COMMERCIAL INSPECTION -1816-1818 WILLISTON AVE. STE
1818 -09/04/
IFOR BILLING INQUIRY: (319)291-4323 1
Description
Total Price I
INSPECTION 2,000
OCCUPANCY FEE
CUSTOMER # BILLING DATE
24829 1 11 / 14/2025
DUE DATE
12/19/2025
City of Waterloo
INVOICE'#
2026-00000209
Less Prepayment
Total Due —>
$70.00
$10.00
CHARGES
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Switch Nutrition - 1816-1820 Williston AVE, BLDG 1816 Williston Ave - STE 1818,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
09/04/2025
Lead Inspector
BRAD BALDWIN
Other Inspectors
N/A
Inspection Type
Annual Inspection (1Yr)
Shift
NIA
425 E. 3rd Street
Inspection Number
17598
Station Unit
N/A N/A
SUMMARY OF INSPECTION
0 34
Passed codes
NEXT STEPS
6
Failed codes
35
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/04/2025 @ 12:41
$80 annual inspection fee.
BRAD BALDWIN - 09/04/2025 @ 13:16
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09/04/2025 @ 13:17
Reinspection Date
10/10/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Brendon Brown Date:
CHECKLISTS
BRAD BALDWIN 09/1112025
GENERATED ON 9/11/25, 7:25 AM 1 OF 5
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Desuription
Location: Back exit
Comments: Remove all obstructions to path of egress to exit path.
Note: not required to maintain path of egress if exit sign is properly
removed or covered as stated in violation 1203.2.6 "Exit Signs"
Description
Location: Front entrance
Comments: Repair or replace exit sign that failed to illuminate during
test.
Location: Back entrance
Comments: Second exit not required due to occupancy load, options:
(1) Repair or replace exit sign that failed to illuminate during test. (2)
Remove exit sign, properly cap wires in covered box or (3) provide
proper cover to exit sign.
GENERATED ON 9/11/25, 7:25 AM 2 OF 5
Electrical Safety
Status Code
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Descriprion
Location: Electric panel closet near back exit
Comments: Replace damaged outlet and provide proper outlet cover.
Location: Bar area
Comments: Remove coffee maker and label machine from power
strip, appliances with heating elements shall be plugged directly to
wall outlet. Power strips allowed for light duty electric only. If adding
outlet, licensed electrical contractor must obtain proper permit and
inspections.
GENERATED ON 9/11/25, 7:25 AM 3 OF 5
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Back storage area near utility sink
Comments: Provide annual service to fire extinguisher, most current
service completed in 2022.