COMMERCIAL INSPECTION - 313 W 5TH ST-10/28/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
21928
BILLING DATE
11/14/2025
DUE DATE
12/19/2025
INVOICE #
2026-00000195
CHARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Club Ambassador - 313 W 5th ST, BLDG 313 W 5th St, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
10/2812025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Othe, Inspectors
N/A
425 E. 3rd Street
Inspection Number
15323
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
039 05
Passed codes Failed codes
NEXT STEPS
0 30
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10/28/2025 @ 14:50
$80 annual inspection fee
BRAD BALDWIN - 10/28/2025 @ 14:54
Corrected during 10/28/25 inspection: Removed power strip daisy chained to another power strip.
BRAD BALDWIN - 10/28/2025 @ 15:03
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
11/2012025
BRAD BALDWIN - 10/28/2025 @ 15:03
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 10/28/2025 @ 15:03
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Nedzad Rekic (2025) Date: BRAD BALDWIN 10/28/2025
CHECKLISTS
GENERATED ON 10/28/25. 3:05 PM 1 OF 6
S
Electrical Safety
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Description
Location: Women"s restroom
Comments: Provide proper blank covering to opening in electric
panel to avoid shock hazard.
Location: Women"s restroom
Comments: Provide permanent sign on restroom door stating
"Electric Room", sign shall be red with white lettering. Laminated
paper will not be accepted.
GENERATED ON 10/28/25, 3:05 PM
2 OF 6
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: Above bar
Comments: Remove power strip from black extension cord. Power
strip must be plugged directly to wall outlet for light duty electric
only.
GENERATED ON 10/28/25, 3:05 PM
3 OF 6
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to all fire extinguishers. Last
current service completed October 2024.
GENERATED ON 10/28/25, 3:05 PM
4 OF 6
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: Bar
Comments: Properly hang fire extinguisher on wall bracket between 4
inches to 5 feet from floor.
GENERATED ON 10/28/25, 3:05 PM
5 OF 6