COMMERCIAL INSPECTION - 2134 LA PORTE RD - 12-16-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22859
12/16/2025
01/19/2026
2026-00000267
$100.00
Less Prepayment
Total Due —►
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Fairfield Inn & Suites - 2134 La Porte RD, BLDG 2134 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
12/1612025
Lead inspector
BRAD BALDWIN
Other Inspectors
NATE BEUSELING
Inspection Type
Annual Inspection (1Yr)
0\
425 E. 3rd Street
Inspection Number
16115
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 47
Passed codes
NEXT STEPS
0 17
Failed codes
0 17
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
01/0912026
BRAD BALDWIN - 12/17/2025 @ 15:30
Corrected during 12116/25 inspection: (1) Removed obstructions to 4th floor west storge room fire extinguisher. (2) Replaced door seal on 3rd floor east
storage room door frame. (3) Replaced door seal on room #204 door frame.
BRAD BALDWIN - 12/17/2025 @ 15:42
Egress lights and exit signs report
ztnrcn ik
nn Ef.e,tiency exit sign s and egIeseemdrganoy
begli n5p4IXed and tire ur working condition.
BRAD BALDWIN - 12/1712025 @ 15:56
Hotel laundry dryer vent cleaning report
GENERATED ON 12/17/25, 3:59 PM 1 OF 7
r Cleaningll t pection
BRAD BALDWIN - 12/17/2025 @ 15:56
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 12/17/2025 @ 15:56
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 12117/2025 @ 15:57
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GM Cindy Huebner - 2025
CHECKLISTS
Date: BRAD BALDWIN 12117/2025
GENERATED ON 12/17/25, 3:59 PM 2 OF 7
Additional Codes
Status
p�Fa�^il
Fail
Fail
Fail
Fail
Fail
Fail
lJ
Code
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
603.1 - General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
603.1 - General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
603.1 - General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Description
Location: All fire doors with new card reader hardware installed.
Comments: Obtain permit and inspections for all work planned or
completed with fire doors. Maintenance person stated today that all
door card readers have been recently replaced.
Location: All new fire door hardware.
Comments: Provide documentation to Waterloo Building Department
for all fire door hardware when applying for permit: 1010.2.9.3
Installation. Where panic or fire exit hardware is installed, it shall
comply with the following: 1. Panic hardware shall be listed in
accordance with UL 305. 2. Fire exit hardware shall be listed in
accordance with UL 10C and UL 305. 3. The actuating portion of the
releasing device shall extend not less than one-half of the door leaf
width. 4. The maximum unlatching force shall not exceed 15 pounds
Location: Water heater
Comments: Contractor (Bergen Plumbing) shall obtain inspection of
work completed. Permit obtained for water heater 8/12/24, no
inspection of record.
Location: Room #317
Comments: Remove furniture cord from lamp receptacle.
Location: Room #206
Comments: Remove TV plugged to lamp receptacle
Location: Room #210
Comments: Remove TV plugged to lamp receptacle
Location: Guest laundry dryers
Comments: Provide documentation of cleaning of dryer vent from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.
GENERATED ON 12/17/25, 3:59 PM 3 OF 7
Fire Sprinkler System
Status Code
Fail
Fail
Fail
5.2.1- Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not Tess
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Description
Location: Sprinkler system
Comments: Provide report uploaded to Compliance Engine of repairs
made to deficiency noted by Blackhawk Automatic Sprinklers, Inc on
6124125
Location: 1st floor guest laundry
Comments: Carefully remove dust build up on sprinkler heads.
Location: 1st floor exercise room
Comments: Carefully remove dust build up on sprinkler heads.
GENERATED ON 12/17/25, 3:59 PM
4 OF 7
Electrical Safety
Status
Fail
0
Fail
Fail
Code
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.8 - Temporary wiring.
Temporary The use of temporary wiring for electrical power
and lighting installations shall not exceed is allowed for a
period not to exceed of 90 days. Temporary wiring methods
shall meet the applicable provisions of NFPA 70. Exception:
Temporary wiring for electrical power and lighting
installations is allowed complying with the applicable
provisions of NFPA 70 is permitted during periods of
construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Fire Resistant Construction Maintenance
Status Code
Fail
l�J
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Cindy's office
Comments: Remove multi -plug adapter, may replace with properly
supported power strip with manual reset for light duty electric only.
Location: 2nd floor electrical room
Comments: Remove extension cord plugged to power strip to IT rack.
IT rack shall be plugged to wall outlet, adding outlet requires licensed
contractor obtain permit and inspection.
Location: Front common area
Comments: Christmas tree lights allowed 90 days, shall be removed
no later than 3/16126
Description
Location: Room #420
Comments: Replace missing smoke seal
GENERATED ON 12/17/25, 3:59 PM 5 OF 7
Portable Fire Extingusihers
Status Code
Fail
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Comments: Provide annual service to all building extinguishers, due
for service January 2026.
Location: 1st floor hotel laundry room
Comments: Remove obstruction from clear access to extinguisher,
maintain clearance at all times.
Location: 2nd floor storage room
Comments: Extinguisher sitting on ground shall be mounted on wall
bracket.
GENERATED ON 12/17/25, 3:59 PM