COMMERCIAL INSPECTION - 428 E 1ST ST - 12-8-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12631
12/16/2025
01/19/2026
2026-00000264
$80.00
Less Prepayment
Total Due
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
\:),(03l
Waterloo Fire Rescue
Inspection Report
Dollar General - 428 E 1st ST, BLDG 428 E 1st St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
12/08/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
19463
Other inspectors
N/A
Shift
N/A
Station
NIA
Unit
NIA
SUMMARY OF INSPECTION
0 35 0 12
Passed codes Faded codes
NEXT STEPS
30
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 12/15/2025 @ 11:49
• $80 annual inspection fee
BRAD BALDWIN - 12/15/2025 @ 13:35
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 12/15/2025 @ 13:35
Reinspection Date
01/1412026
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Tina Peterson (2025) District
CHECKLISTS
Date: BRAD BALDWIN 12/1512025
GENERATED ON 12/15/25, 1:44 PM 1 OF 11
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Rear exit of building
Comments: Remove all objects in exit path, hallway shall be
maintained clear of storage at all times.
GENERATED ON 12/15/25, 1:44 PM 2 OF 11
Additional Codes
S:atus Code
Fail
1018.1 - General.
Aisles and aisle accessways serving as a portion of the exit
access in the means of egress system shall comply with the
requirements of this section. Aisles or aisle accessways shall
be provided from all occupied portions of the exit access that
contain seats, tables, furnishings, displays and similar
fixtures or equipment. The minimum width or required
capacity of aisles shall be unobstructed. Exception:
Encroachments complying with Section 1005.7.
Description
Location: Aisles
Comments: Clear obstructions to aisles. Carts being actively
loaded/unloaded may temporarily block aisles, all other obstructions
shall be maintained clear of aisles at all times.
GENERATED ON 12/15/25, 1:44 PM 3 OF 11
Emergency Equipment
Statu
Fail
0
Fail
Fail
Code
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Emergency egress lights
Comments: Provide documentation of testing all emergency egress
lighting in building including repairs made to maintain working
properly., documentation shall include signature and date of
responsible person.
Location: Exit signs
Comments: Provide documentation of testing all exit signs in
building including repairs made to maintain working properly.,
documentation shall include signature and date of responsible
person.
Location: Rear exit of building
Comments: Exit sign shall be relocated to directly above exit
doorway.
GENERATED ON 12/15/25, 1:44 PM
4 OF 11
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
Location: Rear exit of building
Comments: Double sided exit sign with arrows directing towards rear
exit shall be installed at coiner (attached picture) to direct patrons
towards exit. Licensed electrical contractor shall obtain permit and
inspection of work.
GENERATED ON 12/15/25, 1:44 PM
5 OF 11
General Housekeeping
status Code
Fail
315.3.1- Ceiling clearance.
Storage shall be maintained 2 feet (610 mm) or more below
the ceiling in nonsprinklered areas of buildings or not less
than 18 inches (457 mm) below sprinkler head deflectors in
sprinklered areas of buildings. Exceptions: 1.The 2-foot (610
mm) ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings. 2.The 18-inch (457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1, 903.3.1.2 or
903.3.1.3.
Description
Location: North storage area
Comments: Remove all storage within 24" of ceiling.
GENERATED ON 12/15/25, 1:44 PM
6 OF 11
Electrical Safety
Status Code
Fail 603.4 - Working space and clearancesclearance.
0 A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Electric panel
Comments: Remove storage near electric panel. Maintain 36"
clearance of electric panel at all times.
GENERATED ON 12/15/25, 1:44 PM
7 OF 11
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Descrip5on
Location: Back storage room
Comments: Replace missing ceiling tiles.
GENERATED ON 12/15/25, 1:44 PM
8 OF 11
Portable Fire Extingusihers
Status Code Description
Fail 906.6 - Unobstructed and unobscured.
�.:.1 Portable fire extinguishers shall not be obstructed or Location: Near registers
obscured from view. In rooms or areas in which visual Comments: Remove all items obstructing access to fire extinguisher.
obstruction cannot be completely avoided, means shall be Maintain clear at all times.
provided to indicate the locations of extinguishers.
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: "Employees Only Room"
Comments: Fire Extinguisher shall be properly mounted on wall
bracket in required locations.
GENERATED ON 12/15/25, 1:44 PM
9 OF 11
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,.
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: Bathroom
Comments: Annually serviced fire extinguishers shall be properly
mounted on wall bracket at required locations.