COMMERCIAL INSPECTION - 1422 FLAMMANG - 12-16-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 50,000
OCCUPANCY FEE
$225.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE#
CHARGES
4706
12/16/2025
01/19/2026
2026-00000271
$235.00
Less Prepayment
Total Due — >
City of Waterloo
$0.00
$235.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hy-Vee - 1422 Flammang DR, BLDG 1422 Flammang Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
12116/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16404
5hifl Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
051 024 ®7
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 12117/2025 @ 08:38
$235 annual inspection fee
BRAD BALDWIN - 12/17/2025 @ 09:23
Kitchen hood cleaning due for service 1128126.
BRAD BALDWIN - 12/1712025 @ 11:30
Fire extinguishers due annually serviced by April 2026
BRAD BALDWIN - 12/17/2025 @ 12:21
Egress Lights and Exit Sign report
from
ab...a<iwet at
man ar
a rang , ask artbckwsdearu�arkM Nrvapwoasteaa.
AL eeuix!e i:re dour altN ieare( Wont plrrb,.
Atave main ehvantt to parkwig �qla WMe 8 igeki:
Ahove p,Mw;e w rk slack area bV drop door.
A iea Or {ae aaW[on Auave4MGipdow. above .svAngdwan.Aa4e
awln hW wav- ....
My Vee Fvo Store+
42$➢kmmang Drive
taScrfuo, lA So707
Reinspection Date
01/13/2026
GENERATED ON 12/18/25, 2:55 PM 1 OF 15
BRAD BALDWIN - 12/17/2025 @ 12:30
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 12/17/2025 @ 12:30
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 12/17/2025 @ 12:30
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. ***"*Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Dave Bowling
CHECKLISTS
No signature
Report completed post inspection
n
Date: BRAD BALDWIN 12/1712025
GENERATED ON 12/18/25, 2:55 PM 2 OF 15
Means of Egress
Status Code
Fail
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Exit door near trash compactor
Comments: Repair or replace exit door. Exit door must unlatch and
swing to full open with less than 15 lbs of force. If replaced obtain
permits and inspections.
Location: Liquor store
Comments: Remove obstructions to end of aisle or have licensed
design professional review and provide report to inspector.
GENERATED ON 12/18/25, 2:55 PM
3 OF 15
Emergency Equipment
Status Code
Fail
l^J
1203.4.3 - Records.
Records of the inspection, testing and maintenance of
emergency and standby power systems shall include the date
of service, name of the servicing technician, a summary of
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
Description
Location: Back-up generator
Comments: Provide
GENERATED ON 12/18/25, 2:55 PM 4 OF 15
Fire Sprinkler System
Status Code
Fail
a
Fail
a
Fail
a
5.2.1 - Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Description
Location: Sprinkler system
Comments: Sprinkler system will be past due for annual service prior
to re -inspection as of 1/8/26. Provide annual inspection report with
any deficiencies corrected, contractor must upload report to
Compliance Engine.
Location: Market Grill Kitchen & Deli
Comments: Carefully remove dust build-up on multiple sprinkler
heads.
Location: Old can redemption area
Comments: Remove storage within 18" of sprinkler heads
GENERATED ON 12/18/25, 2:55 PM
5 OF 15
Fail
Fail
Fail
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not Tess
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
903.3.3 - Obstructed locations.
Automatic sprinklers shall be installed with regard to
obstructions that will delay activation or obstruct the water
distribution pattern and shall be in accordance with the
applicable automatic sprinkler system standard that is being
used. Automatic sprinklers shall be installed in or under
covered kiosks, displays, booths, concession stands or
equipment that exceeds 4 feet (1219 mm) in width. Not less
than a 3-foot (914 mm) clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers. Exception: Kitchen equipment under exhaust hoods
protected with a fire -extinguishing system in accordance with
Section 904.
Location: Customer service above lottery machine.
Comments: Carefully remove dust build-up on multiple sprinkler
heads.
Location: Caleb's office (upper level)
Comments: Carefully remove dust build-up on multiple sprinkler
heads.
Comments: An hanging displays obstructing spray patterns of
sprinkler head distribution shall be removed or lowered to 18" below
sprinkler heads .
GENERATED ON 12/18/25, 2:55 PM
6 OF 15
Fire Service Features
Status Code
Fail
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Old can redemption area
Comments: Remove obstructions to clear path of access to fire alarm
pull station.
Location: Main exit sliding glass doors
Comments: Remove gift card stand obstructing fire alarm pull
station.
GENERATED ON 12/18/25, 2:55 PM
7 OF 15
Additional Codes
Status Code
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
603.1 - General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
Description
Location: Back-up generator room
Comments: Secure all compressed gas cylinders (refrigerant) with
chain to avoid tip over.
Location: Starbucks
Comments: Remove ice maker from power strip, appliance shall plug
directly to wall outlet. Adding outlet requires licensed contractor
obtaining permit and inspection.
GENERATED ON 12/18/25, 2:55 PM 8 OF 15
Electrical Safety
Status Code
Fail
O
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Starbucks
Comments: Remove extension cord powering under mounted light,
extension cords are for temporary use only. Flexible wiring shall not
pass through metal fresh air cover as seen in picture.
Location: Outside main walk-in freezer
Comments: Replace missing cover to box.
GENERATED ON 12/18/25, 2:55 PM
9 OF 15
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Exterior (west side of building)
Comments: Repair or replace outlets with missing weather covers.
Location: Wine & Spirits back room
Comments: Remove storage within 30" in total width from panel and
36" in front of. Maintain clearances at all times.
Location: Customer service electrical room
Comments: Remove storage within 30" in total width from panel and
36" in front of. Maintain clearances at all times.
GENERATED ON 12/18/25. 2:55 PM
10 OF 15
FF�aii
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Self checkout closest to "Register 9"
Comments: Power strip shall be mounted to avoid hanging by wires.
Description
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 4 days past due as of 12/17125.
GENERATED ON 12/18/25, 2:55 PM 11 OF 15
Fire Resistant Construction Maintenance
Status Code
Fail
Fail
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2.6 - Testing.
Horizontal and vertical sliding and rolling fire doors shall be
inspected and tested annually to confirm proper operation
and full closure. Records of inspections and testing shall be
maintained.
Description
Location: Upper level sprinkler room
Comments: Replace missing ceiling tile.
Location: Bakery storage
Comments: Provide annual inspection of rolling fire door. Last
current inspection documented 2-4-24.
GENERATED ON 12/18/25, 2:55 PM
12 OF 15
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Sprinkler riser area
Comments: Used fire extinguisher shall be serviced and mounted on
wall bracket in required location
GENERATED ON 12/18/25, 2:55 PM
13 OF 15
Fail
0
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Location: Employee restrooms
Comments: Remove obstructions (crates) from clear unobstructed
access to fire extinguisher. Maintain clearance at all times.