COMMERCIAL INSPECTION - 1956 LAFAYETTE ST - 12-15-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Pricel
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3312
12/16/2025
01/19/2026
2026-00000265
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Cork's Grocery - 1956 Lafayette ST, BLDG 1956 Lafayette St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
12115/2025
Inspection Type
Annual Inspection (1Yr)
331zk/
425 E. 3rd Street
Inspection Number
16420
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Otherinspectors
NIA
SUMMARY OF INSPECTION
0 36
Passed codes
NEXT STEPS
0 12
Failed codes
0 31
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 12/15/2025 @ 15:17
• $80 annual inspection fee
BRAD BALDWIN - 12/16/2025 @ 08:25
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
01/0812026
BRAD BALDWIN - 12/16/2025 @ 08:25
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 12/1612025 @ 08:25
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Shaista Yasmeen
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 12/16/2025
GENERATED ON 12/16/25, 8:29 AM 1 OF 11
General Housekeeping
Status Code
Fail
305.1 - Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Description
Location: Furnace behind Pepsi fountain machine
Comments: Remove storage from within 36" of furnace, maintain
clearance at all times.
GENERATED ON 12/16/25, 8:29 AM
2 OF 11
Additional Codes
Status Code
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Description
Location: Walk-in fridge
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
GENERATED ON 12/16/25, 8:29 AM
3 OF 11
Fail
l�l
603.1- General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
Location: Behind counter near office.
Comments: Remove microwave from power strip. Appliance shall
plug directly to wall outlet.
s
;A1�sP
1 f TAMPONS
GENERATED ON 12/16/25, 8:29 AM
4 OF 11
Electrical Safety
Status Code
Fail
803.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Outlet at end of shelving near Pepsi fountain
Comments: Licensed electrician shall make necessary repairs to
damaged wiring. Keep receipt of work completed to show inspector.
GENERATED ON 12/16/25, 8:29 AM 5 OF 11
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Top of stairs to basement
Comments: Relocate cords to avoid damage from foot traffic and
being pinched in door or provide a Listed Cord Floor Protector over
cords to avoid damage.
Location: Basement near stairs
Comments: Install cover back on junction box
GENERATED ON 12/16/25, 8:29 AM
6 OF 11
Fail
Fail
l�J
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Basement near furnace
Comments: Install knock -out plug in opening in box
Location: Basement near electric panels
Comments: Install missing cover on box
GENERATED ON 12/16/25, 8:29 AM
7 OF 11
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind counter above microwave
Comments: Replace missing outlet cover
Location: Office
Comments: Remove extension cord concealed above drop ceiling.
Extension cords approved for temporary use only.
GENERATED ON 12/16/25, 8:29 AM
8 OF 11
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Descriptk n
Location: Above Pepsi fountain machine
Comments: Replace missing ceiling tiles
GENERATED ON 12/16/25, 8:29 AM
9 OF 11
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to fire extinguishers, currently
due by January 2026.