COMMERCIAL FIRE INSPECTION-1608 UNIVERSITY AVE.,-
11/07/2025
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24828
11/14/2025
12/19/2025
2026-00000216
$100.00
Less Prepayment
Total Due --+
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Green Leaf Tobacco and E-Cigs - 1608 University AVE, BLDG 1608 UNIVERSITY AVE
- STE B, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
1110712025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)_ REINSPECTION
Other Inspectors
NIA
Shift
NIA
o7DY
425 E. 3rd Street
%O ,
Inspection Number
18017-R1
Station Unit
NIA NIA
SUMMARY OF INSPECTION
00 01 010
Passed codes
NEXT STEPS
Resolved violations Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10/09/2025 @ 14:53
$80 annual inspection fee
BRAD BALDWIN - 10/09/2025 @ 14:53
Fire extinguishers due annually serviced in September 2026
BRAD BALDWIN - 10/09/2025 @ 14:53
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
BRAD BALDWIN - 10/09/2025 @ 14:53
Reinspection Date
12/05/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 1110712025 @ 14:41
$100 re -inspection fee, failure to make progress on correcting violations.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
MO 2025 Date: BRAD BALDWIN 11107/2025
CHECKLISTS
GENERATED ON 11/7/25, 2.44 PM 1 OF 7
Additional Codes
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Back exit
Comments: Per occupancy, 2nd exit not required. Would be approved
to remove exit sign or properly cover. Removal requires electric
capped and contained in box with cover. Failure to cover or remove
sign requires removal of interior door obstructing view of exit and
removal of all obstructions to clear access of exit.
GENERATED ON 11/7/25, 2:44 PM 2 OF 7
Reinspection
Status Code Description
Fail 315.3.3 - Equipment rooms.
0 Combustible material shall not be stored in boiler rooms, Location: Mechanical room
mechanical rooms, electrical equipment rooms or in fire Comments: Remove storage from mechanical room, maintain proper
command centers as specified in Section 508.1.5.
Fail
603.1 - General.
Electrical equipment, wiring and systems required by this
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and
Sections 603.2 through 603.10.
clearance at all times.
Additional comments: More storage noted today than last visit.
Location: Near electric panel
Comments: Remove microwave from power strip, appliance shall be
plugged directly to wall outlet.
GENERATED ON 11/7/25, 2:44 PM 3 OF 7
Fail
Fail
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures AU electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: Window lighting
Comments: Provide documentation of proper listing of light fixtures.
Noted "CE" listing as shown in picture not approved for use.
Location: Mechanical room
Comments: Remove cube type multi -plug adapter. May replace with
properly mounted power strip with manual reset plugged directly to
wall outlet for light duty electric only.
GENERATED ON 11/7/25, 2:44 PM
4 OF 7
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Bathroom
Comments: Remove flexible cord to power strip from penetrating
wall.
Location: Under register counter
Comments: Black multi -plug cord not permitted for permanent use.
Would approve to replace with properly mounted power strip with
manual reset for light duty electric only.
GENERATED ON 11/7/25, 2:44 PM
5 OF 7
Fail
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Glass display cabinets
Comments: Remove flexible cord concealed under cabinets running
across walkway IMMEDIATELY. Staff member grabbed cord during
inspection when cord pulled apart from previous damage
Location: Register POS system
Comments: Flexible multi -plug cord used for POS system not
permitted for permanent use. Relocate system to plug to wall outlet
or provide new outlet by licensed electrical contractor by obtaining
permit and inspection. Would approve properly mounted power strip
with manual reset for light duty electric only.
Location: Mechanical room
Comments: Remove tv cord from white extension cord. Would
approve IV plugged to properly mounted power strip with manual
reset plugged directly to wall outlet.