COMMERCIAL FIRE INSPECTION-2250 W. RIDGEWAY AVE.-
11/03/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE#
CHARGES
24570
11/14/2025
12/19/2025
2026-00000222
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Little Stars Child Care Center - 2250 W Ridgeway AVE, BLDG 2250 W Ridgeway Ave,
Waterloo IA 50701
INSPECTION DETAILS
in, petitU)n Date
11103/2025
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
z
Inspection Number
16703
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 46 0 10 0 20
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 11/03/2025 @ 12:21
$80 annual inspection fee
BRAD BALDWIN - 11/03/2025 @ 12:48
Corrected during 11/3/25 inspection: Removed tables obstructing path to exit in "1 year old room"
BRAD BALDWIN - 11/03/2025 @ 12:51
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
BRAD BALDWIN - 11/03/2025 @ 12:51
Reinspection Date
12/0312025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Ibrahim Shehata 2025 Date: BRAD BALDWIN 11103/2025
CHECKLISTS
GENERATED ON 11/3/25, 12:53 PM 1 OF 6
General Housekeeping
Status Code
Fail
Documentation
Status
Fail
0
305.1 - Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5,
Code
403.4.1 - First emergency evacuation drill.
The first emergency evacuation drill of each school year shall
be conducted within 10 days of the beginning of classes.
Fire Service Features
Status Code
Fail
0
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
Additional Codes
Status Code
Fail
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Description
Location: Mechanical room
Comments: Remove storage from within 36" of furnace.
Location: Mechanical room
Comments: Remove combustible storage from room and maintain
clear unobstructed path to electric panel at all times.
Description
Comments: Provide documentation of last fire drill completed. Email
report to inspector.
Description
Comments: If master keys have been changed, notify Fire
Department to update exterior Knox Box
Description
Location: Clothes dryer
Comments: Provide documentation of cleaning of dryer vent from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.
GENERATED ON 11/3/25, 12:53 PM 2 OF 6
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Multi Purpose Room
Comments: Carefully remove paint on fire rating tags without altering
tag information.
GENERATED ON 11/3/25, 12:53 PM
3 OF 6
Fail
Fail
0
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: 3/4 year old room
Comments: Carefully remove paint on fire rating tags without altering
tag information.
Location: Multi Purpose Room
Comments: Remove door wedge holding door open
Location: Manager's office
Comments: Door to front exit hallway failed to self -shut and latch,
repair or replace. Remove foot wedge holding door open.
GENERATED ON 11/3/25, 12:53 PM
4 OF 6
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to all fire extinguishers, last
recorded service completed in January 2024.