COMMERCIAL FIRE INSPECTION-250 WESTFIELD AVE.-
10/27/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 100,000
OCCUPANCY FEE
$600.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23522
11/14/2025
12/19/2025
2026-00000215
$610.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Courtyard by Marriot - 250 Westfield AVE, BLDG 250 Westfield Ave, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
10127/2025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
c).35Dicl
425 E. 3rd Street
(do
Inspection Number
16661
Shift Station Unit
NIA
NIA NIA
SUMMARY OF INSPECTION
060
Passer codes
NEXT STEPS
0 29
Failed codes
2
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10/29/2025 @ 08:12
$610 annual inspection fee
BRAG BALDWIN - 10/29/2025 @ 09:07
Reinspection Date
12/04I2025
Corrected during 10/27/25 inspection: (1) Removed hold open device to 6th floor "Linen" room fire rated door. (2) Removed microwave from power strip in
#520. (3) Removed obstructions to 5th floor chemical storage pool equipment room fire door to allow to self shut and latch.
BRAD BALDWIN - 10/29/2025 @ 08:52
Storage room near #541 locked no access today, provide inspector access at next scheduled inspection.
BRAD BALDWIN - 11110/2025 @ 15:15
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 11/10/2025 @ 15:15
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 11/10/2025 @ 15:15
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 11/10/25, 3:18 PM 1 OF 13
Faith Beebe GM
CHECKLISTS
Means of Egress
Status Code
Fail
Date:
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
Fail
BRAD BALDWIN 11/10/2025
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Main floor back hallway exit
Comments: Remove obstructions (chairs & metal panels) from exit
path. Maintain clear path at all times.
Description
Comments: Provide report of testing all emergency egress lights in
building including repairs if needed. Report shall include signature of
tester and date completed, email report to inspector.
Comments: Provide report of testing all exit signs in building
including repairs if needed. Report shall include signature of tester
and date completed, email report to inspector.
GENERATED ON 11/10/25, 3:18 PM 2 OF 13
Fire Sprinkler System
Status Code
Fail
Fail
lJ
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Additional Codes
Status Code
Fail
0
Fail
0
507.5.3 - Private fire service mains and water tanks.
Private fire service mains and water tanks shall be
periodically inspected, tested and maintained in accordance
with NFPA 25 at the following intervals: 1.Private fire hydrants
of all types: Inspection annually and after each operation;
flow test and maintenance annually. 2.Fire service main
piping: Inspection of exposed, annually; flow test every 5
years. 3.Fire service main piping strainers: Inspection and
maintenance after each use. Records of inspections, testing
and maintenance shall be maintained.
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer&#O39;s operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Desrriptio
Location: Room #609
Comments: Replace missing bathroom escutcheon and repair
bedroom escutcheon loose to ceiling.
Location: Room #337
Comments: Repair loose escutcheon not tight to ceiling
Location: Room #336
Comments: Replace missing sprinkler escutcheon outside bathroom
Description
Location: Private fire hydrant
Comments: Provide report of inspection with any deficiencies
corrected of private fire hydrant on property. Contractor shall upload
report to Compliance Engine. Currently 18 days past due as of
10129/25
Location: All clothes dryers in building
Comments: Provide documentation of cleaning of dryer vents from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.
GENERATED ON 11/10/25, 3:18 PM 3 OF 13
'Electrical Safety
stows Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Deser
ption
Location: 6th floor mechanical room
Comments: Provide cover to ceiling junction box that is missing
Location: Lobby near Iron Horse Saloon
Comments: Contain loose wires in box with appropriate cover
GENERATED ON 11/10/25, 3:18 PM
4 OF 13
Fail
Fail
Fail
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.9.4 - Prohibited areas.
Portable, electric space heaters shall not be operated within 3
feet (914 mm) of any combustible materials. Portable, electric
space heaters shall be operated only in locations for which
they are listed.
603.9.4 - Prohibited areas.
Portable, electric space heaters shall not be operated within 3
feet (914 mm) of any combustible materials. Portable, electric
space heaters shall be operated only in locations for which
they are listed.
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Room #520
Comments: Remove cube style multi -plug adapter under TV. Would
approve properly supported or hung power strip with manual reset
for light duty electric only.
Location: Receptionist desk
Comments: Provide documentation of proper commercial use listing
of appliance or remove from building.
Location: Ben's office
Comments: Provide documentation of proper commercial use listing
of appliance or remove from building. Remove space heater from
power strip.
Description
Location: Kitchen exhaust hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 12 days past due as of 10/29/25
GENERATED ON 11/10/25, 3:18 PM 5 OF 13
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
riptuon
Location: #628 / #629 rooms dividing doors
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
GENERATED ON 11/10/25, 3:18 PM
6 OF 13
Fail
Fail
O
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer&#O39;s installation instructions.
704.1 - Maintaining protection.
Where required when the budding was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: #620 1 #619 rooms dividing doors
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
Location: #519 / #518 dividing room doors
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
GENERATED ON 11/10/25, 3:18 PM
7 OF 13
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Mech room by room #518
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
GENERATED ON 11/10/25, 3:18 PM
8 OF 13
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 4th floor stair tower door near room #441
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
GENERATED ON 11/10/25, 3:18 PM
9 OF 13
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Telecom door near room #425
Comments: Carefully remove tape and/or paint covering fire rating
tags without altering tag information.
GENERATED ON 11/10/25, 3:18 PM
10 OF 13
Fail
Fail
Fail
0
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer&#O39;s installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: #419 / #418 dividing room doors
Comments: Carefully remove tape andlor paint covering fire rating
tags without altering tag information.
Location: 6th floor mechanical room by #601
Comments: Door failed to self shut and latch today, repair or replace.
Location: Room #621
Comments: Door failed to self shut and latch today, repair or replace.
Location: Linen room closet by #512
Comments: Door locked without access today, provide inspector
access to inspect
Location: Room #439
Comments: Door failed to self shut and latch today, repair or replace.
GENERATED ON 11/10/25, 3:18 PM
11 OF 13
Fail
Fail
CD
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Portable Fire Extingusihers
Status
Fail
0
Location: Room #341
Comments: Door failed to self shut and latch today, repair or replace.
Location: Telecom door near room #325
Comments: Door failed to self shut and latch today, repair or replace.
Location: Guest laundry room door to hallway near room #207
Comments: Door failed to self shut and latch today, repair or replace.
Code Description
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Fire extinguishers
Comments: Provide annual service to all extinguishers, currently due
by November 2025.
GENERATED ON 11/10/25, 3:18 PM 12 OF 13