COMMERCIAL FIRE INSPECTION-2035 E. MITCHELL AVE-
11 / 19/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23182
11/24/2025
12/29/2025
2026-00000236
$80.00
Less Prepayment
Total Due
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
nspection Report
King Star • 2035 E Mitchell AVE, BLDG 2035 E Mitchell Ave, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
11/19/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift Station
NIA NIA
425 E. 3rd Street
Ins pec Number
16477
ion
Unit
NIA
SUMMARY OF INSPECTION
034
Passed codes
NEXT STEPS
0 4
Failed codes
36
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN -11119/2025 @ 14:23
$80 annual inspection fee
BRAD BALDWIN - 11119/2025 @ 15:23
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 11/1912025 @ 15:23
Reinspection Date
12111/2025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 11119/2025 @ 15:23
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Muhammad Bhatti
CHECKLISTS
No signature
Report completed post inspection
13E
Date: BRAD BALDWIN 11119/2025
GENERATED ON 11/19/25, 3:26 PM 1 OF 5
Means of Egress
St ids C
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Rear exit
Comments: Clear obstructions in path to access exit. Maintain clear
path at all times.
Description
Location: Rear exit
Comments: Repair or replace exit sign that failed to illuminate during
test.
GENERATED ON 11/19/25, 3:26 PM 2 OF 5
Additional Codes
tdt=:y Cod
Fail
2305.2.2 - Repairs and service.
The fire code official is authorized to require damaged or
unsafe containment and dispensing equipment to be repaired
or serviced in an approved manner.
Description
Location: Pump #4
Comments: Weathered/cracked filler hose shall be replaced.
GENERATED ON 11/19/25, 3:26 PM
3 OF 5
Portable Fire Extingusihers
St tu3 Co-"
Fail 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Rear of building (exterior)
Comments: Provide annual service to fire extinguisher, last service
recorded in 2020.