COMMERCIAL FIRE INSPECTION-2034 LA PORTE RD-11/24/2025
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
11/24/2025
12/29/2025
2026-00000232
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
11/24/2025
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr) �REINSPECTION
Other inspectors
N/A
425 E. 3rd Street
Inspection Number
13671-R11
Shift Station Unit
NIA N/A NIA
SUMMARY OF INSPECTION
O 0 o 1 8
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN -10/27/2025 @ 07:40
$200 re -inspection fee, failure to correct deficiencies as of 8/22/25.
BRAD BALDWIN - 10/27/2025 @ 07:40
$200 Re -inspection fee for failure to correct violations on 6/23/25
BRAD BALDWIN - 10/27/2025 @ 07:40
Provide corrections to avoid re -inspection fees
BRAD BALDWIN - 10/27/2025 @ 07:40
Annual inspection $235
BRAD BALDWIN - 10/27/2025 @ 07:40
Provide corrections to avoid re -inspection fees.
BRAD BALDWIN - 10/27/2025 @ 07:40
Re -inspection fee $100
BRAD BALDWIN - 10/27/2025 @ 07:40
Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for completion of fire door certifications.
BRAD BALDWIN -10/27/2025 @ 07:40
Re -inspection fee $150
BRAD BALDWIN - 10/27/2025 @ 07:40
Called Mitch on 4/17/25 and he stated no improvement.
BRAD BALDWIN - 10/27/2025 @ 07:40
Re -inspection fee $200
Reinspection Date
12/17/2025
GENERATED ON 11/24/25, 7:42 AM
1 OF 7
BRAD BALDWIN - 1012712025 @ 07:40
annual inspection $200
BRAD BALDWIN - 10/27/2025 @ 07:40
We are recommending denial of alcohol license to the City Council because of lack of progress on required certification of guest room fire doors that
were altered during construction.
BRAD BALDWIN - 1012712025 @ 07:40
$200 Re -inspection fee, failure to complete corrections as of 7122125
BRAD BALDWIN - 1012712025 @ 07:40
$200 re -inspection fee, failure to correct deficiencies or provide plan to make corrections as of 10/3/25.
BRAD BALDWIN - 10127/2025 @ 07:40
Withholding re -inspection fee today due to progress made 10124125
BRAD BALDWIN - 11124/2025 @ 07:38
$200 re -inspection fee, failure to complete corrections as of 11/24125. Discussion with Cayenne on site (11120125) regarding lack of fire doors re-
certification report.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cayenne Adams - Manager (2025)
CHECKLISTS
Rt
Date: BRAD BALDWIN 1112412025
GENERATED ON 11/24/25, 7:42 AM
2 OF 7
Reinspection
Status Code
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Entire buiding
Comments: Obtain permits and inspections for all work concerning
fire door repair, replacement smoke seals, all hardware replaced.
Please see original attached email with codes concerning information
requiered for fire door hardware. Please contact Building Official
Greg Ahlhelm with questions. 319-291-4319
Location: Entire second floor guest fire doors
Comments: Install approved smoke seal in all fire door openings that
has been removed including stair doors and utility areas. Check all
other floors
Location: Entire Second Floor
Comments: verify all removed smoke seals have been replaced on
second floor. Also 4th floor and all other smoke sweeps added to
bottom of doors must be verified as listed for fire doors and
inspected.
GENERATED ON 11/24/25, 7:42 AM
3 OF 7
Fail 704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: obtain permit and inspections
GENERATED ON 11/24/25, 7:42 AM
4 OF 7
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Comments: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent
smokelfire from inflitrating fire rated coridoor.
GENERATED ON 11/24/25, 7:42 AM
5 OF 7
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids ih the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: Stairway Fire Door by room 330
Comments: Repair fire door. There is a gap at bottom of door. Must
completely seal
Location: 1st floor west stair tower door
Comments: Fire rated door altered by cutting bottom of door as
shown in picture. Either replace door by obtaining permit and
inspection or obtain architect to review door, report from architect
shall be sent to inspector.
Additional comments: No progress made as of 11/20125
Location: 1st floor hallway men's bathroom
Comments: Door failed to shut and latch from full open position.
Bottom of door drags and sticks on ground.
Additional comments: No progress made as of 11/20125