COMMERCIAL FIRE INSPECTION-2141 LA PORTE RD-11/19/2025
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22996
11/24/2025
12/29/2025
2026-00000225
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Motel 6 - 2141 La Porte RD, BLDG 2141 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
1111912025
Lead Inspector
JEREMIAH VANDYKE
Other Inspectors
NIA _
Inspection Type
Annual Inspection (1Yr)
SUMMARY OF INSPECTION
039 08 028
Passed codes Failed codes NIA codes
Shift
NIA
Station
NIA
diacig(p
425 E. 3rd Street
veo
In.pection Number
16351
Unit
NIA
NEXT STEPS Reinspection Date
Please direct questions about your Inspection to: 1211912025
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 1111912025 @ 15:03
Clothes dryers cleaned in house and logged 71612025.
JEREMIAH VANDYKE - 1111912025 @ 15:14
61212025 S - (Annual) Fire Alarm PER MAR SECURITY SERVICES Reviewed Compliant
JEREMIAH VANDYKE - 1111912025 @ 15:14
121212024 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed Compliant
JEREMIAH VANDYKE - 1111912025 @ 15:15
typically ti performed
Re -inspection dates are automatically generated 30 days
out
enerated re- initial
spectioninspection.
date ands oNormal
n a weeoperating
kendothe re inspection w tI typnsp Y tlolp ar
Monday -Friday, 8:00 a.m. - 5:00 p.m. If the automatically 9 ou can call to set up an earlier re -inspection. *****Re inspection fees
the following Monday or Tuesday. If all corrections are made before the 30 days, y
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE -1111912025 @ 15:15
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE -1111912025 @ 15:15
Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
SIGNATURES
Inspector signature
Contact signature
No signature
Report completed post inspection
GENERATED ON 11/19/25, 3:20 PM
1 OF 4
Pinky Patel
CHECKLISTS
Emergency Equipment
Status Code
Fail
Fail
Date:
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
Additional Codes
Status Code
Fail
1103.8 - Single- and multiple -station smoke alarms.
Single- and multiple -station smoke alarms shall be installed
in existing Group 1-1 and R occupancies in accordance with
Sections 1103.8.1 through 1103.8.3.
General Housekeeping
Status Cod:
Fail
315.3.3 - Equipment rooms.
Combustible material shall not be stored in boiler rooms,
mechanical rooms, electrical equipment rooms or in fire
command centers as specified in Section 508.1.5.
JEREMIAH VANDYKE
11/19/2025
Description
Location: 1. Laundry room ceiling. 2. Lobby area near front door. 3.
Egress light near room 229.
Comments: Egress lights were tested and failed. Need to repair or
replace.
Location: 1. Front entrance lobby area. 2. Lower floor exit light near
room 124.
Comments: Exit lights were teste and failed. Need to repair or
replace.
Description
Location: Rooms #: 131, 134, 139, 141, 221, 225, 226, 227, 228, 235,
237, 239, 243, 245, 247.
Comments: Smoke detectors were either not working, missing, or
hanging from wires. Need to repair or replace.
Description
Location: Sprinkler riser room.
Comments: Need to clear storage from sprinkler riser/mechanical
room.
GENERATED ON 11/19/25, 3:20 PM
2 OF 4
Fire Resistant Construction Maintenance
stat-us code
Fail
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers.. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Portable Fire Extingusihers
sawGode
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Checking all doors to hotel guest rooms.
Comments: Multiple doors are missing part of the door seal that is
required.
Location: Room: 131, 133, 139, 141, 225, 228, 233, 237, 238, 243, 245,
246, 247.
Comments: Marked fire doors of hotel guest rooms need to shut and
latch from full swing. Need to repair or adjust doors to close properly.
Location: 2nd floor east stair door not closing. Need to repair or
adjust. Self closer was pulled out of wall.
Comments: 2nd floor east stair door not closing. Need to repair or
adjust. Self closer was pulled out of wall.
Description
Location: All fire extinguishers are past due. Need to contact fire
extinguisher contractor to inspect and re tag.
Comments: All fire extinguishers are past due. Need to contact fire
extinguisher contractor to inspect and re tag.