COMMERCIAL FIRE INSPECTION-2343 LOGAN AVE-11/17/2025
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6265
11/24/2025
12/29/2025
2026-00000224
$100.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Motel 6 - 2343 Logan AVE, BLDG 2343 Logan Ave, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
11/17/2025
Lead Inspector
JEREMIAH VANDYKE
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
co,
Inspection Number
15597
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
039
Passed codes
NEXT STEPS
8
Failed codes
28
NIA codes
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 11/17/2025 @ 11:16
11/3/2025 S - (Annual) Fire Alarm HAWKEYE ALARM Reviewed Deficient
JEREMIAH VANDYKE - 11/17/2025 @ 11:16
1/3/2025 S - (Annual) Fire Sprinkler BLACKHAWK AUTOMATIC SPRINKLERS, INC. Reviewed Compliant
JEREMIAH VANDYKE - 11/17/2025 @ 11:17
Reinspection Date
12/17/2025
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday - Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be performed
the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection.'**** Re inspection fees
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 11/17/2025 @ 11:17
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 11/17/2025 @ 11:17
Inspection Fee = $100.00 (To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 11/17/25, 11:20 AM 1 OF 6
Arp Patel Date:
CHECKLISTS
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Additional Codes
Status Code
Fail
Fail
l:J
1103.8 - Single- and multiple -station smoke alarms.
Single- and multiple -station smoke alarms shall be installed
in existing Group 1-1 and R occupancies in accordance with
Sections 1103.8.1 through 1103.8.3.
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Fire Alarm System
Status Code
Fail
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
Description
Location: Pool area.
Comments: ExitlEgress light above south door tested and failed.
Need to replace or repair.
Description
Location: Rooms # 114, 206, 214, 217, 218, 223.
Comments: Smoke alarms were tested and failed or missing. Need to
repair or replace.
Location: Hotel guest clothes dryers and hotel's large dryer.
Comments: Clothes Dryer Exhaust Duct system must be cleaned
from the dryer to the outside DOCUMENTED by who and when
serviced.
Description
Location: Deficiency on Compliance engine needs addressed and
updated by contractor. Contact fire alarm contractor to address
deficiency as soon as possible.
Comments: Deficiency Found: Answer: Fire alarm has a sprinkler
system that is not monitored
GENERATED ON 11/17/25, 11:20 AM 2 OF 6
Electrical Safety
Status Code
Fail
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: 103 behind bed.
Comments: Green Extension cord plugged into power strip. Can not
daisy chain.
GENERATED ON 11/17/25, 11:20 AM
3 OF 6
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Fire Resistant Construction Maintenance
..,atus
Fail
Code
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Location: 103 Behind bed.
Comments: Can not use green extension cord as permenant wiring.
D St,'i;pTtOn
Location: 1st floor and 2nd floor north hallway doors to steps and
middle hallways both levels had door stops holding marked fire
doors open. Discussed getting mag locks installed by fire alarm
contractor.
Comments: 1st floor and 2nd floor north hallway doors to steps and
middle hallways both levels had door stops holding marked fire
doors open. Discussed getting mag locks installed by fire alarm
contractor.
GENERATED ON 11/17/25, 11:20 AM 4 OF 6
Portable Fire Extingusihers
Status Cede
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Fire extinguishers are past due and need to be inspected
by licensed extinguisher contractor and re tagged.
Comments: Fire extinguishers are past due and need to be inspected
by licensed extinguisher contractor and re tagged.
GENERATED ON 11/17/25, 11:20 AM 5 OF 6