COMMERCIAL INSPECTION - 1410 FLAMMANG DR - 8-26-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15097
09/05/2025
10/15/2025
2026-00000105
$80.00
Less Prepayment
Total Due ->
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hardee's - 1410 Flammang DR, BLDG 1410 Flammang Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
08/26/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
c1i
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
1096
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 46 GO 9
Passed codes Failed codes
NEXT STEPS
23
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/26/2025 @ 12:45
$80 annual inspection fee
BRAD BALDWIN - 08/26/2025 @ 12:48
Kitchen hood suppression system due for service on 9/23/25.
BRAD BALDWIN - 08/26/2025 @ 13:13
Fire extinguishers due annually serviced March 2026.
BRAD BALDWIN - 08/26/2025 @ 13:35
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 08/2612025 @ 13:35
Reinspection Date
09/18/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Eic
John Kelchen (2025) Regional Date: BRAD BALDWIN 08/26/2025
CHECKLISTS
GENERATED ON 8/26/25, 1:37 PM 1 OF 6
Additional Codes
Status Code Description
Fail 102.4 - Application of building code.
0 The design and construction of new structures shall comply Location: Water heater installation
with the International Building Code ,and any alterations, Comments: Obtain plumbing permit and inspection of water heater
additions, changes in use or changes in structures required installed without permit by Heartland Gaskets.
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
AUTOMATIC STORAGE WATER NEATER
VENT INSTALLATR)k
3T fi"f
CSAIANSI Z.t1.Vp,11CSA 4,1-2011
bNv an9 L99341132 INA
90 _ • IS
Location: Hood exhaust control panel
12111929921
Comments: Relocate shelf to avoid obstructing access to panel,
maintain clear path.
GENERATED ON 8/26/25, 1:37 PM
2 OF 6
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
606.3.1 - Ventilation system.
The ventilation system in connection with hoods shall be
operated at the required rate of air movement, and grease
filters listed and labeled in accordance with UL 1046 shall be
in place where equipment under a kitchen grease hood is
used.
Location: CO2 storage
Comments: Secure compressed gas cylinder with chain to avoid tip
over.
Location: Kitchen flat top hood filters
Comments: Close gaps in grease filters. Filters not in place cause
more grease in ductwork and on cables for fire supression.
GENERATED ON 8/26/25, 1:37 PM
3 OF 6
General Housekeeping
Sta[uua cod,
Fail
Fail
l_J
304.3.1- Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
305.1 - Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Fire Service Features
Status Code
Fail
505.1 - Address identification.
New and existing buildings shall be provided with approved
address identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 mm) high with a minimum stroke
width of 1/2 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
Location: Water heater
Comments: Remove and maintain clearance within 36 " from water
heater
D
Comments: Provide address identification numbers in contrast with
building.
GENERATED ON 8/26/25, 1:37 PM
4 OF 6
Fire Resistant Construction Maintenance
Status Code
Fail
l^J
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Office
Comments: Replace missing ceiling tile.
Location: Front vestibule
Comments: Replace missing ceiling tile.