COMMERCIAL INSPECTION - 900 LA PORTE RD - 8-25-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
13176
09/05/2025
10/15/2025
2026-00000098
$80.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Chapalas - 900 La Porte RD, BLDG 900 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection I:)w'
08125/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift Station
NIA NIA
425 E. 3rd Street
Inspection Number
14845
Unit
N/A
SUMMARY OF INSPECTION
�. 55
Passed codes
NEXT STEPS
06
Failed codes
15
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/25/2025 @ 12:10
$80 annual inspection fee
BRAD BALDWIN - 08/2512025 @ 12:23
Fire extinguishers due for annual service December 2025.
BRAD BALDWIN - 08/25/2025 @ 12:28
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
Reinspection Date
09/19/2025
BRAD BALDWIN - 08/25/2025 @ 12:28
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 08/2512025 @ 12:28
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jael Arceo owner 2025 Date: BRAD BALDWIN 08/2512025
CHECKLISTS
GENERATED ON 8/25/25, 12:31 PM 1 OF 4
Electrical Safety
Status rode
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: Kitchen bathroom
Comments: Provide missing cover to outlet.
Location: Near ATM
Comments: Remove yellow 3-way multi -plug adapter. May replace
with power strip with manual reset plugged to wall outlet properly
mounted or supported, use only for light duty electric.
Location: Outdoor seating
Comments: Remove white multi -plug extension cord from exterior
lighting.
Location: Tea drink station
Comments: Multi -plug cord and multi -plug adapter shall be removed.
May replace with power strip with manual reset, properly mounted or
supported for Tight duty electric. Appliances shall be plugged directly
to wall outlet.
GENERATED ON 8/25/25, 12:31 PM
2 OF 4
Additional Codes
Status Code
Fail
606.2 - Where required.
A Type 1 hood shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used
for commercial purposes that produce grease vapors.
Exceptions: 1.Factory-built commercial exhaust hoods that
are listed and labeled in accordance with UL 710, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 710B, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code. Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code. For the
purpose of determining the floor area required to be
ventilated, each individual appliance shall be considered as
occupying not less than 100 square feet (9.3 m2). 3.Where
cooking appliances are equipped with integral down -draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96, a hood shall not be required at or above them. 4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mglm3
or less of grease when tested at an exhaust flow rate of 500
cfm (0.236 m3ls) in accordance with UL 710B.
Fire Resistant Construction Maintenance
status
Fail
Code
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions,
Description
Location: Single burner range
Comments: Relocate cooking equipment producing grease laden
vapors to be within 6 inches inside of outer edges of hood exhaust
system.
Description
Location: Kitchen office
Comments: Install missing ceiling tiles to maintain fire protection.
GENERATED ON 8/25/25, 12:31 PM