COMMERCIAL INSPECTION - 840-844 W 4TH ST - 8-28-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
9015
09/05/2025
10/15/2025
2026-00000117
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Tri-County Child & Family Development Council - 840 - 844 W 4th ST, BLDG 844 W
4th st, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
08/28/2025
Lead Inspector
JEREMIAH VANDYKE
Inspection Type
Annual Inspection (1Yr)
c�5
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
15480
Shift Station Unit
N/A N/A NIA
SUMMARY OF INSPECTION
059 06 Q8
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 08/28/2025 @ 12:27
Fire Extinguisher serviced by Hawkeye Fire and Safety October 2024.
JEREMIAH VANDYKE - 08/28/2025 @ 12:28
Dryers cleaned by Harris Cleaning 3/11/2025.
JEREMIAH VANDYKE - 08/28/2025 @ 12:29
Discussed the use of space heaters.
Reinspection Date
09/27/2025
JEREMIAH VANDYKE - 08/28/2025 @ 12:47
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday - Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be performed
the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. "**"*Re inspection fees
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 08/28/2025 @ 12:47
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 08/28/2025 @ 12:48
Inspection Fee = $80.00 (To be mailed out by City via snail mail)
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 8/28/25, 12:49 PM 1 OF 4
Pauline Jones Date:
CHECKLISTS
Means of Egress
Status Code
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
Documentation
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Sidles code
Fail
405.6 - Recordkeeping.
Records shall be maintained of required emergency
evacuation drills and include the following information:
1.ldentity of the person conducting the drill. 2.Date and time
of the drill. 3.Notification method used. 4.Employees on duty
and participating. 5.Number of occupants evacuated.
6.Special conditions simulated. 7.Problems encountered.
8.Weather conditions when occupants were evacuated.
9.Time required to accomplish complete evacuation.
Descriptio/
Location: Door #4 double doors.
Comments: 1 side of the double doors would not open. Need to
repair.
Description
Location: South side basement area.
Comments: Multiple egress lights in basement failed. Will be
repairing or replacing.
Description
Location: Fire drill needs to be done and recorded.
Comments: Fire drill needs to be done and recorded.
GENERATED ON 8/28/25, 12:49 PM 2 OF 4
Electrical Safety
Status Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fire Resistant Construction Maintenance
Status
Fail
Description
Location: South basement near Safe room in hallway.
Comments: Open electrical box hanging through open ceiling grid.
Location: Nurses station.
Comments: Daisy chanined powerstrips need to be removed. Need to
remove.
Code Description
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof!ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 1st floor and basement.
Comments: Multiple ceiling tiles are missing and will be replaced
after roof leaks are addressed. Roof is currently under construction.