COMMERCIAL INSPECTION - 620 W 5TH ST - 9-25-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
24073
10/22/2025
01/09/2026
2026-00000175
CHARGES
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Royal Legacy Christian Academy- Legacy Littles - 620 W 5th ST, BLDG 620 W 5th St,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
09/25/2025
Lead Inspector
Inspection Type
Annual Inspection (1Yr)
C):.- 5 E.3rd Street
Inspection Number
15439
Station Unit
JEREMIAH VANDYKE N/A NIA NIA
Other lnspectors
N/A
SUMMARY OF INSPECTION
050 06 ®17
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE - 09/2512025 @ 15:24
Fire extinguishers serviced by Superior Fire September 2025.
JEREMIAH VANDYKE - 09/25/2025 @ 15:25
AED needs to be serviced.
JEREMIAH VANDYKE - 09125/2025 @ 15:25
Fire drill completed for daycare and school 9/12/2025.
JEREMIAH VANDYKE - 09125/2025 @ 15:26
All life safety systems compliant on Compliance engine.
JEREMIAH VANDYKE - 09125/2025 @ 15:27
Clothes Dryer vent cleaned and recorded 9/4/2025.
Reinspection Date
10125/2025
JEREMIAH VANDYKE - 09/25/2025 @ 15:36
Re -inspection dates are automatically generated 30 days out from the initial inspection. Normal operating hours for inspections & re -inspections are
Monday - Friday, 8:00 a.m. - 5:00 p.m. If the automatically generated re -inspection date lands on a weekend, the re -inspection will typically be performed
the following Monday or Tuesday. If all corrections are made before the 30 days, you can call to set up an earlier re -inspection. *****Re inspection fees
may be assessed for subsequent re -inspections. Re -inspection fees start at $100, then $150, and $200 for all subsequent re-inspections.-
JEREMIAH VANDYKE - 09/25/2025 @ 15:36
Lt. Van Dyke - jeremiah.vandyke@waterloo-ia.org - Work: 319-291-4460 - Cell: 319-883-1615
JEREMIAH VANDYKE - 09/25/2025 @ 15:36
Inspection Fee = $80.00 (To be mailed out by City via snail mail)
SIGNATURES
Contact signature Inspector signature
GENERATED ON 9/25/25, 3:37 PM
1 OF 4
No signature
Report completed post inspection
Brian Dolan Date:
CHECKLISTS
Emergency Equipment
Status Code
Fail
Fail
JEREMIAH VANDYKE
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fire Sprinkler System
Status Code
Fail 4.9 - Support of nonsprinkler system components
OSprinkler system components shall not be used to support
non -sprinkler system components unless expressly permitted
by NFPA 13.
Electrical Safety
Status Code
Fail 603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
09/25/2025
Location: 1. 3rd floor 2. West steps near the Vybrary door.
Comments: Egress light tested and failed. Need to repair or replace
Location: 3rd floor
Comments: Exit lights tested and failed. Need to repair or replace.
Description
Location: Spanish class room
Comments: Flags hanging from sprinkler lines that must be removed.
Description
Location: Mrs. Andorfs room.
Comments: Fridge plugged into powerstrip. Need to have fridge
plugged directly into power strip.
GENERATED ON 9/25/25, 3:37 PM
2 OF 4
Fire Resistant Construction Maintenance
Ccde
Fail
Fail
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Gym
Comments: Ceiling tiles missing that need replaced.
Location: Marked fire doors on east side of building.
Comments: Remove door stops on marked fire doors. Advise that
they must remain shut at all times. Discussed getting magnetic hold
open devices installed by fire alarm contractor to keep doors open.
GENERATED ON 9/25/25, 3:37 PM