COMMERCIAL INSPECTION - 1850 W RIDGEWAY - 9-25-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23310
10/22/2025
01/09/2026
2026-00000180
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
1850 Patio Grill - 1850 W Ridgeway AVE, BLDG 1850 W Ridgeway Ave - STE 5,
Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
09/25/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
14801
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
056 ®10 ®10
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/2512025 @ 15:21
$80 annual inspection fee
BRAD BALDWIN - 09/25/2025 @ 15:23
Fire extinguishers due annually serviced by December 2025.
BRAD BALDWIN - 09/25/2025 @ 15:37
West side exterior seating christmas lights not currently plugged in. Approved for 90 day usage when in use.
BRAD BALDWIN - 09/30/2025 @ 10:21
Superior serviced hood Suppression serviced June 2025
BRAD BALDWIN - 09/30/2025 @ 10:22
AKA serviced hood exhaust cleaning June 2025
BRAD BALDWIN • 09130/2025 @ 10:55
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/23(2025
BRAD BALDWIN - 09/30/2025 @ 10:55
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 09/30/2025 @ 10:55
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
GENERATED ON 9/30/25, 11:07 AM 1 OF 8
No signature
Report completed post inspection
Marcus Phillips 2025 Date:
CHECKLISTS
BRAD BALDWIN 09130/2025
Means of Egress
Status erode Description
Fail 1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be Location: Kitchen exit door
continuously maintained free from obstructions or Comments: Remove obstructions to exit path, maintain clear egress
impediments to full instant use in the case of fire or other at all times.
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
GENERATED ON 9/30/25, 11:07 AM
2 OF 8
Fire Service Features
Status Cede
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Additional Codes
Status Cade
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Near back door to patio seating
Comments: Relocate plant in front of alarm pull station.
Description
Location: Bar
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: Outdoor seating string lights
Comments: Provide documentation of proper listing of light fixtures.
GENERATED ON 9/30/25, 11:07 AM
3 OF 8
Electrical Safety
Status code
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: North outdoor seating outlets
Comments: Provide proper covers to outlet boxes
GENERATED ON 9/30/25, 11:07 AM
4 OF 8
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Kitchen mechanical room
Comments: Remove tubs from room, maintain 36" clearance in front
of panels at all times for emergency access.
GENERATED ON 9/30/25, 11:07 AM
5 OF 8
Fail 603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: North patio seating
Comments: Remove green cube style multi -plug adapter.
Location: North patio seating
Comments: Flexible wiring to string lights concealed in ceiling shall
be removed from concealed spaces. Extension cords allowed for
temporary use only. Permanent wiring shall be installed by licensed
electrical contractor with obtaining permit and inspection.
GENERATED ON 9/30/25, 11:07 AM
6 OF 8
Fire Resistant Construction Maintenance
Status Coda
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Kitchen mechanical room
Comments: Replace missing ceiling tile above water heater.
Location: Front vestibule
Comments: Replace missing ceiling tiles.
GENERATED ON 9/30/25, 11:07 AM 7 OF 8