KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1625 W 4TH ST - 10-6-25
FOR BILLING INQUIRY: (319)291-4323
I Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
13354
10/22/2025
01/09/2026
2026-00000170
$80.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
New Star - 1625 W 4th ST, BLDG 1625 W 4th St, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
10/06/2025
Lead lnspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
15060
Shift Station Unit
N/A N/A N/A
SUMMARY OF INSPECTION
0 33 0 8 ® 35
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10107/2025 @ 08:58
$80 annual inspection fee
BRAD BALDWIN - 10/07/2025 @ 09:11
Fire extinguishers due annually serviced in January 2026
BRAD BALDWIN - 10/07/2025 @ 09:25
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/29/2025
BRAD BALDWIN - 10/07/2025 @ 09:25
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 10/07/2025 @ 09:25
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Mamoon Amhtar 2025
CHECKLISTS
No signature
Report completed post inspection
3R
Date: BRAD BALDWIN 10/07/2025
GENERATED ON 10/7/25, 9:27 AM 1 OF 7
Additional Codes
,.a.,,.. Code
Fail 5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Outdoor propane cabinet
Comments: Replace missing hazard identification signage. Currently
sitting on ground next to cabinet, not visible.
Location: Outdoor window lighting
Comments: Provide documentation of proper listing of use for light
fixtures. Markings noted on fixtures does not approve for use in U.S.
Remove if not properly listed.
LJ
GENERATED ON 10/7/25, 9:27 AM
2 OF 7
Electrical Safety
Stat 3 Code
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Ice cream chest cord
Comments: Licensed electrical contractor shall repair or replace
appliance cord. Copy of receipt of work completed shall be kept and
sent to inspector.
Location: Beer fridge fan
Comments: Replace missing cover to box
GENERATED ON 10/7/25, 9:27 AM
3 OF 7
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Location: Liquor storage electric panels
Comments: Panel covers shall be permanently screwed shut to avoid
access to wire connections.
GENERATED ON 10/7/25, 9:27 AM 4 OF 7
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Liquor storage room ("ATM" electric panel)
Comments: Remove obstructions within 36" in front of electric panel
continuing down to floor. Maintain clearance at all times.
Location: Near register counter
Comments: Remove black flexible cord concealed in ceiling. If adding
permanent wiring or outlet, licensed electrical contractor must obtain
proper permit and inspection.
GENERATED ON 10/7/25, 9:27 AM
5 OF 7
Portable Fire Extingusihers
u.v
Fail
906.6 - Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or
obscured from view. In rooms or areas in which visual
obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Description
Location: Near front entrance
Comments: Remove obstructions to access to fire extinguisher,
maintain clear path at all times.
GENERATED ON 10/7/25, 9:27 AM 6 OF 7
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number
NIA
Check Number Transaction Number
N/A NIA
GENERATED ON 10/7/25, 9:27 AM
7 OF 7