COMMERCIAL INSPECTION - 210 E TOWER PARK - 10-10-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3085
10/22/2025
01/09/2026
2026-00000176
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
N►.1 Inspection Report
Sam's Club - 210 E Tower Park DR, BLDG 210 E Tower Park Dr, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
10/1012025
Inspection Type
Annual Inspection (1Yrj REINSPECTION
425 E. 3rd Street
Inspection Number
12174-R9
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 C) 4
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
10/31/2025
BRAD BALDWIN - 09119/2025 @ 07:38
$200 re -inspection fee, failure to correct any deficiencies as of 8/28/25. Re -inspection fee's will continue until corrections are completed.
BRAD BALDWIN - 09/19/2025 @ 07:38
Provide correctins to avoid re -inspection fees
BRAD BALDWIN - 09/19/2025 @ 07:38
annual inspection $600
BRAD BALDWIN - 09/19/2025 @ 07:38
Fire door drop test 5/13/24
BRAD BALDWIN - 09/1912025 @ 07:38
Fire pump maintenance Elite 2/20/24
BRAD BALDWIN - 09/1912025 @ 07:38
Fire Alarm inspection due 3/19/25
BRAD BALDWIN - 09/1912025 @ 07:38
hood fire suppression due 3/30/25
BRAD BALDWIN - 09/19/2025 @ 07:38
Provide corrections to avoid $100 re -inspection fee.
BRAD BALDWIN - 09119/2025 @ 07:38
No fee today because some work completed. Fees will apply if all corrections not completed.
BRAD BALDWIN - 09/19/2025 @ 07:38
Failure to correct violations may result in re -inspections fees
GENERATED ON 10/10/25, 7:54 AM 1 OF 4
BRAD BALDWIN - 09/19/2025 @ 07:38
RE-inspeciton fee $100
BRAD BALDWIN - 09/19/2025 @ 07:38
$150 re -inspection fee, failure to correct violations as of 7117/25.
BRAD BALDWIN - 09119/2025 @ 07:38
$200 re -inspection fee for failure to correct violations.
BRAD BALDWIN - 09/19/2025 @ 07:38
$200 re -inspection fee, failure to correct any deficiencies as of 9/19I25. Re -inspection fee's will continue until corrections are completed.
BRAD BALDWIN - 10110/2025 @ 07:52
$200 re -inspection fee for failing to make corrections as of 10/10/25.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Josh Marx - Club Manager
CHECKLISTS
Ef s)
Date: BRAD BALDWIN 10110/2025
GENERATED ON 10/10/25, 7:54 AM 2 OF 4
Reinspection
Sta .... Code
Fail
Fail
Fail
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
507.5.3 - Private fire service mains and water tanks.
Private fire service mains and water tanks shall be
periodically inspected, tested and maintained in accordance
with NFPA 25 at the following intervals: 1.Private fire hydrants
of all types: Inspection annually and after each operation;
flow test and maintenance annually. 2.Fire service main
piping: Inspection of exposed, annually; flow test every 5
years. 3.Fire service main piping strainers: Inspection and
maintenance after each use. Records of inspections, testing
and maintenance shall be maintained.
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
901.6 - Inspection, testing and maintenance.
Fire detection and alarm systems, emergency alarm systems,
gas detection systems, fire -extinguishing systems,
mechanical smoke exhaust systems and smoke and heat
vents protection and life safety systems shall be maintained
in an operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection and life
safety systems and equipment shall be inspected, tested and
maintained or removed in accordance with Section 901.8
Description
Location: Exit door by eco lab # 7 aid case of shell oil
Comments: Repair exit door. Exit door must unlatch and swing to full
open with less than 15# force. Door would not open at all today. If
replaced obtain permits and inspectcions.
Location: Private fire hydrant
Comments: Service for hydrant now 28 days past due as of 6126/25.
Private hydrants need to be inspected by licensed contractor and
report uploaded to Compliance engine by contractor
Location: Kitchen hood exhaust system
Comments: Provide quarterly hood exhaust cleaning with report
uploaded by contractor to Compliance Engine. Currently 15 days past
due as of 817/25.
Location: Fire sprinkler system
Comments: Provide report of repair to deficiency noted in report #
7847909 on 8/15/25. 2" drain line is leaking
GENERATED ON 10/10/25, 7:54 AM 3 OF 4