COMMERCIAL INSPECTION - 2822 UNIVERSITY AVE - 7-10-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24745
07/11/2025
08/15/2025
2026-00000034
$80.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Mi Guanajuato - 2822 University AVE, BLDG 2822 University Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
07110/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
y5 Nei-0
425 E. 3rd Street
Inspection Number
5557
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
045
Passed codes
NEXT STEPS
011 ®21
Failed codes NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 07/10/2025 @ 10:50
$80 annual inspection fee
BRAD BALDWIN - 07/10/2025 @ 13:26
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
08/07/2025
BRAD BALDWIN - 07/10/2025 @ 13:27
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 07/10/2025 @ 13:27
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
ARACELI CARRILLO 2025
CHECKLISTS
Date: BRAD BALDWIN 07/1112025
GENERATED ON 7/11/25, 7!32 AM 1 OF 7
Additional Codes
Status Code
Fail
Fail
1010.2.1 - Unlatching.
The unlatching of any door or leaf for
egress shall require not require more than one operation
motion in a single linear or rotational direction to release all
latching and all locking devices. Exceptions: 1.Places of
detention or restraint. 2.Where manually operated bolt locks
are permitted by Section 1010.2.5. 3.Doors with automatic
flush bolts as permitted by Section 1010.2.4, Item 3 4. 4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4, Item 4 5.
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
Emergency Equipment
staius Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Rear kitchen door
Comments: Repair push -bar to properly operate or would approve to
remove push -bar.
Location: Overhang/roof/siding replaced.
Comments: Permit holder shall request and pass inspection of work
completed.
Description
Location: All emergency egress lighting
Comments: Repair or replace egress lighting that failed to illuminate
during testing.
Location: Front entrance exit sign
Comments: Repair or replace exit sign that failed to illuminate during
testing.
GENERATED ON 7/11/25, 7:32 AM 2 OF 7
Electrical Safety
Slaws Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Dining area near (south) thermostat
Comments: Outlet shall be properly installed in box with appropriate
cover.
Location: Mechanical room behind door
Comments: Provide appropriate cover installed on box.
GENERATED ON 7/11/25, 7:32 AM
3 OF 7
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Commercial Cooking Hood Suppression System
"xtittrs Code
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Mechanical room
Comments: Remove obstructions within 36" in front of electric panel.
Description
Location: Kitchen exhaust hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 1513 days past due as of 7110/25.
Location: Kitchen exhaust hood system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 1515 days past due as of 7/10/25.
GENERATED ON 7/11/25, 7:32 AM
4 OF 7
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1 - Maintaining protection.
l 1 Where required when the building was originally constructed, Location: Near mechanical room
materials and systems used to protect joints and voids in the Comments: Replace missing ceiling tiles outside mechanical room
following locations shall be maintained. The materials and door
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 7/11/25, 7:32 AM 5 OF 7
Portable Fire Extingusihers
Status Code
Fail
l:J
906.1 - Where required.
Portable fire extinguishers shall be installed in all of the
following locations: 1.In new and existing Group A, B, E, F, H,
I, M, R-1, R-2, R-4 and S occupancies. Exceptions: 1.In Group
R-2 occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C. 2.In Group E
occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C. 3. In storage areas of Group
S occupancies where forklift, powered industrial truck or
powered cart operators are the primary occupants, fixed
extinguishers, as specified in NFPA 10, shall not be required
where in accordance with all of the following: 3.1. Use of
vehicle -mounted extinguishers shall be approved by the fire
code official. 3.2. Each vehicle shall be equipped with a 10-
pound, 40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use. 3.3. Not less than
two spare extinguishers of equal or greater rating shall be
available on -site to replace a discharged extinguisher. 3.4.
Vehicle operators shall be trained in the proper operation, use
and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30
feet (9144 mm) distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group I-
1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed. 4.On each floor of structures under
construction, except Group R-3 occupancies, in accordance
with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but
not limited to laboratories, computer rooms and generator
rooms, where required by the fire code official. Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.
Description
Comments: Provide two required, serviced fire extinguishers
installed on wall brackets no less than 4" from the floor & no more
than 5feet from the floor in height. Maximum 75 ft distance between
extinguishers.
GENERATED ON 7/11/25, 7:32 AM 6 OF 7