COMMERCIAL INSPECTION - 3026 ANSBOROUGH AVE - 7-2-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 1
Total Price
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24742
07/11/2025
08/15/2025
2026-00000035
$100.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Pink Cloud Smoke Shop - 3026 Ansborough AVE, BLDG 3026 Ansborough Ave -
STE B, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
07/0212025
Lead Inspector
BRAD BALDWIN
inspection Type
Annual Inspection (lYr) `REINSPECTION.
Other Inspectors
NIA
Shift
NIA
3 (--r) Li 2-
425 E.3rd Street
Inspection Number
8038-R1
Station Unit
NIA NIA
SUMMARY OF INSPECTION
CJ o
Passed codes
NEXT STEPS
0 9
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
5 @ 10:08
spection fee)
BRAD BALDWIN - 06/26/2025 @ 10:08
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
07/17/2025
BRAD BALDWIN - 06/26/2025 @ 10:08
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 06/26/2025 @ 10:08
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 07102/2025 @ 12:50
$100 re -inspection fee on 712124ilure to remove bed from property, air bed was actively deflating during inspection, noted signs of staff sleeping night
prrOr: W bedding shall be removed from building. Re -inspection fees may be assessed daily if bedding remains in building.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Aftab Afribi (2025) Date: BRAD BALDWIN 07/02/2025
CHECKLISTS
GENERATED ON 7/2/25, 12:51 PM 1 OF 6
Reinspection
Sxatus Cod
Fail
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
102.3 - Change of use or occupancy.
A change of occupancy shall not be made unless the use or
occupancy is made to comply with the requirements of this
code and the International Existing Building Code
Exception: Where approved by the fire code official, a change
of occupancy shall be permitted without complying with the
requirements of this code and the International Existing
Building Code , provided that the new or proposed use or
occupancy is Tess hazardous, based on life and fire risk, than
the existing use or occupancy.
Description
Location: Back exit door
Comments: Repair or replaced door, required special force to open. If
replaced, obtain proper building permit and inspections by licensed
contractor.
Location: Back storage room
Comments: NO SLEEPING IN BUILDING. REMOVE ALL BEDDING
AND MATRESSES IMMEDIATELY
GENERATED ON 7/2/25, 12:51 PM
2 OF 6
Fail
Fail
Fail
Fail
315.3.2 - Means of egress.
Combustible materials shall not be stored in exits or
enclosures for stairways and ramps. Combustible materials in
the means of egress during construction, demolition,
remodeling or alterations shall comply with Section 3312.3.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Back storage exit
Comments: Remove pallet from path of egress.
Comments: Several wire splices noted throughout store shall be
removed and replaced with permanent wiring by licensed electrical
contractor by obtaining permits and inspections.
Comments: Appliances shall be directly plugged into wall outlet.
Power strips shall be properly mounted on wall surface or supported
to avoid hanging by wires, power strips shall not lay across walking
surface.
Location: Electrical panel room
Comments: Replace missing ceiling tiles
GENERATED ON 7/2/25, 12:51 PM 3 OF 6
Fail
Fail
0
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Bathroom
Comments: Replace missing ceiling tiles
Location: Back storage rooms
Comments: Replace missing ceiling tiles
GENERATED ON 7/2/25, 12:51. PM 4 OF 6
Fail
J
906.1- Where required.
Portable fire extinguishers shall be installed in all of the
following locations: 1.In new and existing Group A, B, E, F, H,
1, M, R-1, R-2, R-4 and S occupancies. Exceptions: 1.In Group
R-2 occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C. 2.In Group E
occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C. 3. In storage areas of Group
S occupancies where forklift, powered industrial truck or
powered cart operators are the primary occupants, fixed
extinguishers, as specified in NFPA 10, shall not be required
where in accordance with all of the following: 3.1. Use of
vehicle -mounted extinguishers shall be approved by the fire
code official. 3.2. Each vehicle shall be equipped with a 10-
pound, 40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use. 3.3. Not less than
two spare extinguishers of equal or greater rating shall be
available on -site to replace a discharged extinguisher. 3.4.
Vehicle operators shall be trained in the proper operation, use
and inspection of extinguishers. 3.5. Inspections of vehicle -
mounted extinguishers shall be performed daily. 2.Within 30
feet (9144 mm) distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group I-
1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed. 4.On each floor of structures under
construction, except Group R-3 occupancies, in accordance
with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but
not limited to laboratories, computer rooms and generator
rooms, where required by the fire code official. Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.
Comments: Provide two fire extinguishers properly installed on wall
brackets, extinguishers shall be installed within 75 feet of the next.
Self purchased extinguishers shall have copy of receipt to show
purchase date, contractor purchased extinguishers provide required
tag.
GENERATED ON 7/2/25, 12:51 PM 5 OF 6