COMMERCIAL INSPECTION - 117 E SAN MARNAN DR - 7-10-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24676
07/11/2025
08/15/2025
2026-00000037
$200.00
Less Prepayment
Total Due -*
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
The Spot #3 - 117 E San Marnan DR, BLDG 117 E San Marnan Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
07/10/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
REINSPECTION 16174-R6
Other Inspectors
NIA
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 0 0 5 0 3
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 06/17/2025 @ 15:34
$200 re -inspection fee for failure to correct violations as of 6/11/25
BRAD BALDWIN - 06/17/2025 @ 15:34
-Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
08/01/2025
BRAD BALDWIN - 06117/2025 @ 15:34
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -inspection fees
start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 06/17/2025 @ 15:34
annual inspection $80
BRAD BALDWIN - 06/17/2025 @ 15:34
Re -inspection fee $100
BRAD BALDWIN - 06/17/2025 @ 15:34
fees increase each re -inspection incremently to $200
BRAD BALDWIN - 06/17/2025 @ 15:34
Re -inspection fee $150
BRAD BALDWIN - 06/17/2025 @ 15:34
provide all corrections to avoid further re -inspection fees.
BRAD BALDWIN - 06/17/2025 @ 15:34
No re -inspection fee today because some progress made. Provide ALL corrections to avoid re -inspection fees at next inspection.
BRAD BALDWIN - 07/1112025 @ 06:56
GENERATED ON 7/11/25, 6:58 AM 1 OF 6
$200 re -inspection fee on 7110125
SIGNATURES
Contact signature Inspector signature
Malik (2025)
CHECKLISTS
No signature
Report completed post inspection
.1-,LE,
Date: BRAD BALDWIN 07111/2025
GENERATED ON 7/11/25, 6:58 AM 2 OF 6
Reinspection
status Code
Fail
l;1
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Near fountain soda machines
Comments: Remove freezer cord from aisle walkway area to avoid
trip and shock hazard.
Additional comments: Freezer cord has been altered, obtain licensed
electrician to repair appliance cord, email copy of receipt of repair
from contractor to inspector. Remove conduit containing appliance
cord on floor and install approved cord protector (see attachments).
GENERATED ON 7/11/25, 6:58 AM 3 OF 6
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Back storage
Comments: Remove obstructions within required clearances to
electric panel.
Additional comments: Storage still in front of panel on 7/10/25
GENERATED ON 7/11/25, 6:58 AM
4 OF 6
Additional Codes
Status Code
Fail
0
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Beverage fridge at end of cashier counter
Comments: Appliance cord has been altered, obtain licensed
electrician to repair cord, email copy of receipt of repair from
contractor to inspector.
GENERATED ON 7/11/25, 6:58 AM 5 OF 6