COMMERCIAL INSPECTION - 117 E SAN MARNAN DR - 8-8-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLINGDATE
DUE DATE
INVOICE #
CHARGES
24676
08/08/2025
09/15/2025
2026-00000063
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
The Spot#3 117 E.San Marnan DR, BLDG 117 E San Marnan Dr, Waterloo IA 50702
INSPECTION DETAILS
inspection Date
0810812025
Lead Inspector
BRAD BALDWIN
a(4 (p
425 E. 3rd Street
Inspection Type Inspection Number
Annual Inspection (1Yr)
*BMW EGTIt)N 16174-R7
Other Inspectors
N/A
Shitt
NIA
Station Unit
N/A NIA
SUMMARY OF INSPECTION
O 0
Passed codes
NEXT STEPS
0
Resolved violations
0 5
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/08/2025 @ 08:09
$200 re -inspection fee for failure to correct violations as of 6111/25
BRAD BALDWIN - 07/1112025 @ 06:58
-Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
08/29/2025
BRAD BALDWIN - 07/1112025 @ 06:58
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. ****"Re inspection fees may be assessed for subsequent re -inspections. Re -inspection fees
start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 07/1112025 @ 06:58
annual inspection $80
BRAD BALDWIN - 07/11/2025 @ 06:58
Re -inspection fee $100
BRAD BALDWIN - 07/1112025 @ 06:58
fees increase each re -inspection incremently to $200
BRAD BALDWIN - 07/11/2025 @ 06:58
Re -inspection fee $150
BRAD BALDWIN - 07/11/2025 @ 06:58
provide all corrections to avoid further re -inspection fees.
BRAD BALDWIN - 07111/2025 @ 06:58
No re -inspection fee today because some progress made. Provide ALL corrections to avoid re -inspection fees at next inspection.
BRAD BALDWIN - 07111/2025 @ 06:58
GENERATED ON 8/825, 8:19 AM 1 OF 5
$200 re -inspection fee on 7/10125
BRAD BALDWIN - 08/08/2025 @ 08:10
$200 re -inspection fee for failure to correct violations as of 8/7/25
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Malik (2025)
CHECKLISTS
-ER
Date: BRAD BALDWIN 08/0812025
GENERATED ON 8/8/25, 8:19 AM
2 OF 5
Additional Codes
Status Code
Fail
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
5304.1 - Upright storage.
Compressed gas containers, cylinders and tanks, except
those designed for use in a horizontal position, and all
compressed gas containers, cylinders and tanks containing
nonliquefied gases, shall be stored in an upright position with
the valve end up. An upright position shall include conditions
where the container, cylinder or tank axis is inclined as much
as 45 degrees (0.80 rad) from the vertical. Exceptions: 1.
Compressed gas containers with a water volume less than 1.3
gallons (5 L) are allowed to be stored in a horizontal position.
2.Cylinders, containers and tanks containing nonflammable
gases, or cylinders, containers and tanks containing
nonliquefied flammable gases that have been secured to a
pallet for transportation purposes.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Back storage shelf near electrical panel
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: CO2 tank back storage
Comments: Tank laying horizontal on shelf shall be upright and
chained to prevent tip over
Location: Back storage near electrical panel
Comments: Replace all missing ceiling tiles.
GENERATED ON 8/8/25, 8:19 AM 3 OF 5
Reinspection
status code.
Fail
Fail
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: Beverage fridge at end of cashier counter
Comments: Appliance cord has been altered, obtain licensed
electrician to repair cord, email copy of receipt of repair from
contractor to inspector.
Additional comments: No documentation of electrical contractor
repairs. Electrical inspector has not been contacted as of 8/8/25.
Location: Near fountain soda machines
Comments: Remove freezer cord from aisle walkway area to avoid
trip and shock hazard.
Additional comments: No documentation of electrical contractor
repairs. Electrical inspector has not been contacted as of 8/8/25.
GENERATED ON 8/8/25, 8:19 AM
4 OF 5
Statement of Fees
FEE
Invoice Date
NIA
Inspection Fee
$200.00
Date Paid Amount Paid
Invoice Number Check Number Transaction Number
NIA NIA N/A