COMMERCIAL INSPECTION - 2034 LA PORTE RD - 7-23-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 3
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
08/08/2025
09/15/2025
2026-00000058
$200.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Hampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
INSPECTION DETAILS
inspection Date
07/23/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
REINSP€CTIQN
Ocher inspectors
NIA
Shift
NIA
425 E. 3rd Street
Inspection Number
13671-R7
Station Unit
NIA NIA
SUMMARY OF INSPECTION
() 0 0 4 0 13
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 06/24/2025 @ 15:23
$200 Re -inspection fee for failure to correct violations on 6123/25
BRAD BALDWIN - 06/24/2025 @ 15:23
Provide corrections to avoid re -inspection fees
BRAD BALDWIN - 06/24/2025 @ 15:23
Annual inspection $235
BRAD BALDWIN - 06/24/2025 @ 15:23
Provide corrections to avoid re -inspection fees.
BRAD BALDWIN - 06/24/2025 @ 15:23
Re -inspection fee $100
BRAD BALDWIN - 06124/2025 @ 15:23
Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for completion of fire door certifications.
BRAD BALDWIN - 06124/2025 @ 15:23
Re -inspection fee $150
BRAD BALDWIN - 06/2412025 @ 15:23
Called Mitch on 4117125 and he stated no improvement.
BRAD BALDWIN - 06/2412025 @ 15:23
Re -inspection fee $200
BRAD BALDWIN - 06124/2025 @ 15:23
annual inspection $200
Reinspection Date
08/2212025
GENERATED ON 7/23/25, 7:33 AM 1 OF 9
BRAD BALDWIN - 06124/2025 @ 15:23
We are recommending denial of alcohol license to the City Council because of lack of progress on required certification of guest room fire doors that
were altered during construction.
BRAD BALDWIN - 07/23/2025 @ 07:31
$200 Re -inspection fee, failure to complete corrections as of 7/22125
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
_ETS
Cayenne Adams - Manager Date: BRAD BALDWIN 07/2312025
CHECKLISTS
GENERATED ON 7/23/25, 7:33 AM 2 OF 9
Reinspection
Status Coda
Fail
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
5.2.1- Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7,Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
0
Location: Entire buiding
Comments: Obtain permits and inspections for all work concerning
fire door repair, replacement smoke seals, all hardware replaced.
Please see original attached email with codes concerning information
requiered for fire door hardware. Please contact Building Official
Greg Ahlhelm with questions. 319-291-4319
Location: Annual Standpipe insepction deficiencies
Comments: Provide current annual fire sprinkler stand pipe
inspection report wth all discrepancies corrected. Current report lists
2 discrepancies. Contractor must upload corrections online to the
compliance engine.
Additional comments: One deficiency remains to be corrected as of
7/22125
Location: Room 300
Comments: replace missing eschutcheon above sink
Additional comments: Room occupied on 7/22/25
Location: Entire second floor guest fire doors
Comments: Install approved smoke seal in all fire door openings that
has been removed including stair doors and utility areas. Check all
other floors
GENERATED ON 7/23/25, 7:33 AM 3 OF 9
Fail
(TO
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the Additional comments: Permit obtained, no inspections on file as of
construction. 1.Joints in or between fire -resistance -rated 7/22/25
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the budding was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Guest Computer Room
Comments: patch sheetrock ceiling with sheetrock. Mud and tape
joints.
Location: Stairway Fire Door by room 330
Comments: Repair fire door. There is a gap at bottom of door. Must
completely seal
GENERATED ON 7/23/25, 7:33 AM 4 OF 9
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Comments: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent
smoke/fire from inflitrating fire rated coridoor.
GENERATED ON 7/23/25, 7:33 AM
5 OF 9
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail
0
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: obtain permit and inspections
Location: Entire Second Floor
Comments: verify all removed smoke seals have been replaced on
second floor. Also 4th floor and all other smoke sweeps added to
bottom of doors must be verified as listed for fire doors and
inspected.
GENERATED ON 7/23/25, 7:33 AM 6 OF 9
Fail
0
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
Location: 1st floor outside of elevators
Comments: Repair ceiling with sheetrock, mud and tape. Staff did
indicate more ceiling will need removed to complete leak on sprinkler
pipe. Repair will require a permit and inspection.
Location: 2nd Floor laundry inside door
Comments: Repair fire door. Fire door must completely self -close and
latch. Upper part of door does not properly seal.
Additional comments: Door shuts and latches. Door does not
properly seal.
Location: Annual Fire Alarm Inspection
Comments: Provide current semi-annual fire alarm inspection report
with all discrepancies corrected. Currently 106 days past due.
Contractor must upload online to the compliance engine.
Additional comments: Make corrections to 3 deficiencies noted on
Compliance Engine
GENERATED ON 7/23/25, 7:33 AM
7 OF 9
Additional Codes
Status Code
Fail 5.2.1.1.5 - Missing escutcheons
l J Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Oesrripiton
Location: 2nd floor electrical room.
Comments: Replace missing escutcheon from sprinkler head.
GENERATED ON 7/23/25, 7:33 AM