COMMERCIAL INSPECTION - 4018 UNIVERSITY AVE - 8-5-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
3448
BILLING DATE
08/08/2025
DUE DATE
09/15/2025
INVOICE #
2026-00000054
CHARGES
$80.00
Less Prepayment
Total Due
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
3
u�
Waterloo Fire Rescue
Inspection Report
Casey's 218 Pub - 4010 - 4018 University AVE, BLDG 4010 - 4018 University Ave,
Waterloo IA 50701
INSPECTION DETAILS
Inspection Dam
08/05/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
14747
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 42 0 12 Q 22
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/05/2025 @ 13:44
$80 annual inspection fee
BRAD BALDWIN - 08106/2025 @ 07:02
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 08/0612025 @ 07:02
Reinspection Date
08/2712025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 08/06/2025 @ 07:02
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jeremy Ades 2025 Date:
CHECKLISTS
BRAD BALDWIN 08/0612025
GENERATED ON 8/6/25, 7:06 AM 1 OF 8
Emergency Equipment
Cedes Code
Fail
Fail
Fail
0
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Pool hall (west side) near Busch Light neon sign
Comments: Repair or replace emergency egress lighting that failed to
illuminate during testing.
Location: Pool hall (west)
Comments: Repair or replace exit sign above SW exterior exit door
that failed to illuminate during testing.
Location: Exterior beer garden
Comments: Repair or replace exit sign that failed to illuminate during
testing.
GENERATED ON 8/6/25, 7:06 AM 2 OF 8
Electrical Safety
Status Code
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
D -scription
Location: Arcade area mechanical room
Comments: Remove obstructions within 36" of electric panel,
maintain clear path.
Location: Arcade area checkout stand
Comments: Remove power tap from power tap, plug directly to wall
outlet.
GENERATED ON 8/6/25, 7:06 AM
3 OF 8
((Fail
0
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Location: Pool hall (west)
Comments: Remove power strip from power strip, plug directly to
wall outlet.
Location: Arcade area mechanical room
Comments: Properly mount power strip on wall or support on shelf to
avoid hanging by wires.
GENERATED ON 8/6/25, 7:06 AM 4 OF 8
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.8 - Temporary wiring.
Temporary The use of temporary wiring for electrical power
and lighting installations shall not exceed is allowed for a
period not to exceed of 90 days. Temporary wiring methods
shall meet the applicable provisions of NFPA 70. Exception:
Temporary wiring for electrical power and lighting
installations is allowed complying with the applicable
provisions of NFPA 70 is permitted during periods of
construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Location: Pool hall (west)
Comments: Properly hang power strip on ceiling to avoid hanging by
wires.
Location: Pool hall (west)
Comments: Christmas lights allowed temporarily for 90 days, must
be taken down by 914/25.
GENERATED ON 8/6/25, 7:06 AM 5 OF 8
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIIIKECA C1O.
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer&#O39;s installation instructions.
Location: Kitchen hood exhaust system
Comments: Clean grease filters
oe,cription
Location: Front vestibule
Comments: Replace missing ceiling tiles.
GENERATED ON 8/6/25, 7:06 AM 6 OF 8
Portable Fire Extingusihers
Status Cede
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to all fire extinguishers, last
serviced February 2024.
GENERATED ON 8/6/25, 7:06 AM
7 OF 8
Statement of Fees
FEE
Invoice Date Inspection Fee
N/A $80.00
Invoice Number
NIA
Date Paid Amount Paid
Check Number Transaction Number
N/A NIA
GENERATED ON 8/6/25, 7:06 AM