COMMERCIAL INSPECTION - 4550 LA PORTE RD - 7-29-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 20,000
OCCUPANCY FEE
$90.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15249
08/08/2025
09/15/2025
2026-00000053
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Bamboo Ridge - 4550 La Porte RD, BLDG 4550 La Porte Road, Waterloo IA 50702
INSPECTION DETAILS
n Date
07/29/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
15408
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 44
Passed codes
NEXT STEPS
0 12
Failed codes
0 23
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 07/29/2025 @ 11:12
Fire extinguishers due annually serviced September 2025.
BRAD BALDWIN - 07/29/2025 @ 15:29
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
BRAD BALDWIN - 07129/2025 @ 15:29
Reinspection Date
08/21/2025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 07129/2025 @ 15:29
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 07/29/2025 @ 15:32
S100..atinuaioinstietthtinItee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Matt Abben (2025) Date: BRAD BALDWIN 07/29/2025
CHECKLISTS
GENERATED ON 7/29/25, 3'32 PM 1 OF 4
Additional Codes
Status
Fail
l:d
Fail
Fail
102.4 - Application of budding code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
610.1.2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Emergency Equipment
Status Gode
Fail
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: 2 park model homes by bath house
Comments: Obtain building and electrical permits and inspections for
installation of park models, decks, and electrical
Location: Gas station electrical room
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: Commercial and guest clothes dryers
Comments: Provide documentation of cleaning of dryer vent from
appliance to the outside of the building with signature and date.
Email documentation to fire inspector.
Description
Location: Gas station electric room
Comments: Repair or replace egress lighting that failed to illuminate
during testing.
Location: Wai women's shower room
Comments: Repair or replace egress lighting closest to shower that
failed to illuminate during testing.
Location: Wai men's shower room
Comments: Repair or replace both egress lights that failed to
illuminate during testing.
Location: Lua men's shower room
Comments: Repair or replace egress lighting closest to showers that
failed to illuminate during testing.
GENERATED ON 7/29/25, 3:32 PM
2 OF 4
Electrical Safety
Status Code
Fail
Fail
0
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Wai shower house
Comments: Install appropriate cover to east exterior outlet.
Location: Maintenance garage
Comments: Remove obstructions within 36" of electric panel,
maintain clear path.
Location: Gas station near ATM
Comments: Remove multi -plug adapter, may replace with power strip
with manual reset.
Location: Gas station ITlsump pump room
Comments: Remove power strip plugged to other power strip near
sump pump.
Location: Maintenance garage mechanical room
Comments: Remove extension cord to deep freezer. Relocate freezer
to plug directly to wall outlet or provide new outlet by licensed
contractor with permits and inspections obtained.
GENERATED ON 7/29/25, 3:32 PM
3 OF 4
Statement of Fees