COMMERCIAL INSPECTION - 3551 UNIVERSITY AVE - 7-31-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
24760
08/08/2025
09/15/2025
2026-00000052
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Aspire Dance Studio - 3551 University
50701
INSPECTION DETAILS
E, BLDG 3551 University Ave, Waterloo IA
g(tibi/e)
425 E. 3rd Street
Inspection Date Inspection Type Inspection Number
07/31/2025 Annual Inspection (1Yr) 17368
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other inspectors
NIA
SUMMARY OF INSPECTION
045
Passed codes
NEXT STEPS
U 18 ® 20
Fallen codes N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 07/3112025 @ 15:27
$80 annual inspection tee
BRAD BALDWIN - 07/31/2025 @ 15:27
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 07/31/2025 @ 15:27
Reinspection Date
08/27/2025
It all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 07/31/2025 @ 15:28
• -Contact Black Hawk County Dispatch of any changes for emergency 24 hour contacts in the event of an emergency at that address. Phone # 319-291-
2515.
BRAD BALDWIN - 08104/2025 @ 08:22
Fire extinguishers due annually serviced by Sept 2025
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Alexis Roling Date:
CHECKLISTS
BRAD BALDWIN 08/04/2025
GENERATED ON 8/4/25. 8:30 AM 1 OF 8
Means of Egress
Status Code
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Description
Location: Rear exit door
Comments: Repair or replace door to allow door to open with less
than 15lbs of force. If replacement of door is necessary, permit and
inspections shall be obtained.
GENERATED ON 8/4/25, 9:30 AM 2 OF 8
Emergency Equipment
>taius Code
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Outside Dance Shop
Comments: Repair or replace lights that failed to illuminate during
testing.
Location: Outside Studio 2
Comments: Repair or replace lights to operate as manufactured.
Location: Studio 2 bathroom
Comments: Repair or replace lighting to operate as manufactured.
Fail 1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress Location: Above receptionist desk
illumination in accordance with Sections 1008.3 and 1104.5.1.
Comments: Repair or replace egress lights that failed to illuminate
during testing.
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Dancers lounge
Comments: Repair or replace lights that failed to illuminate during
testing.
Location: Front lobby men's bathroom
Comments: Repair or replace lights near mechanical room that failed
to illuminate during testing.
GENERATED ON 8/4/25, 9:30 AM 3 OF 8
Fail
Fail
Fail
x
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress Location: Dancer's lounge bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments: Repair or replace lights to operate as manufactured.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not Tess than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fire Sprinkler System
status Code
Fail
5.2.1.1.5 - Missing escutcheons
Escutcheons and coverplates for recessed, flush, and
concealed sprinklers shall be replaced if found missing
during the inspection.
Fire Service Features
Status Code
Fail
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
Location: Front lobby women's bathroom
Comments: Repair or replace lights near showers that failed to
illuminate during testing.
Location: Studio 2 exterior exit door
Comments: Repair or replace exit sign and egress lights that failed to
illuminate during testing.
Location: Studio 2
Comments: Repair or replace exit sign and egress lights that failed to
illuminate during testing.
Description
Location: Front vestible
Comments: Escutcheon loose to ceiling shall be tight to ceiling.
Description
Location: Near front entrance
Comments: Contact Fire Department to update Knox Box with current
keys to access building in emergency.
GENERATED ON 8/4/25, 9:30 AM 4 OF 8
Electrical Safety
Status Code
Fail
603.4 - Working space and clearancesciearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Near rear exit
Comments: Maintain clear path and 36" clearance around electric
panel.
GENERATED ON 8/4/25, 9:30 AM
5 OF 8
Fire Resistant Construction Maintenance
Status Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
Status
FailF(/
Fail
Code
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Several fire rated doors within space.
Comments: Remove all paint or any obstruction to fire door tags.
Tags must not be altered and shall maintain legible.
Description
Location: Parent viewing room
Comments: Fire extinguisher shall be properly mounted on wall
bracket within 4" to 5' from floor.
Location: Dance shop
Comments: Fire extinguisher shall be properly mounted on wall
bracket within 4" to 5' from floor.
GENERATED ON 8/4/25, 9:30 AM
6 OF 8
Additional Codes
Status Code
Fail
0
907.4.2.6 - Unobstructed and unobscured.
Manual fire alarm boxes shall be provided with ready access,
unobstructed, unobscured and visible at all times.
Description
Location: Near rear exit
Comments: Remove obstructions to clear path of fire alarm pull
station.