COMMERCIAL INSPECTION - 2206 KIMBALL AVE - 8-13-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 3
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3423
08/18/2025
09/20/2025
2026-00000079
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Family Dollar - 2206: Kimball AVE, BLDG 2206 Kimball Ave, Waterloo IA 50701
INSPECTION DETAILS
z3
425 E. 3rd Street
Inspection Date Inspection Type Inspection Number
08/13/2025 Annual Inspection (1Yr) _j REINSPECTION 1 10713-R8
Lead inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 ® 03
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 07/18/2025 @ 12:28
annual inspection $80
BRAD BALDWIN - 07/18/2025 @ 12:28
No storage allowed in aisles for stock. One aisle has boxes of merchandise along one side.
BRAD BALDWIN - 07/18/2025 @ 12:28
correct all violations to avoid progressive re -inspection fees beginning at $100.
BRAD BALDWIN - 07/18/2025 @ 12:28
re -inspection fee $100. provide all corrections to avoid $150 re -inspection fee at next visit.
BRAD BALDWIN - 07/18/2025 @ 12:28
re -inspection fee $150
BRAD BALDWIN - 07/18/2025 @ 12:28
Re -inspection fee $200
BRAD BALDWIN - 07/18/2025 @ 12:28
$200 re -inspection fee for failure to correct deficiencies on 6/26/25
BRAD BALDWIN - 07/18/2025 @ 12:28
Withholding re -inspection tee on 7/18/25. Failure to complete corrections in timely manner may result fees.
BRAD BALDWIN - 08/13/2025 @ 15:17
$209,re-inspection fee for failure to correct violations on 8/13/25.
SIGNATURES
Contact signature
GENERATED ON 8/13/25, 3:19 PM
Inspector signature
Reinspection Date
09/0412025
1 OF 3
No signature
Report completed post inspection
JoAnne Mitchell Date:
CHECKLISTS
BRAD BALDWIN 08113/2025
Reinspection
Status Code Description
Fail
Fail
Fail
0
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: outside of building above back (west) exit door
Comments: repair outside egress light.
Location: Back wall of store above paper goods
Comments: repair exit light.
Location: Basement
Comments: Provide annual service to extinguisher, last serviced
March 2024.