HomeMy WebLinkAbout2935 LOGAN AVEINVOICE DATE
DUE DATE.
INVOICE #
TOTAL DUE
08/18/2025
09/20/2025
2026-00000071
$150.00
Customer #: 15560
DOLLAR GENERAL
100 MISSION RIDGE
GOODLETTSVILLE, TN 37072
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 2935 LOGAN AVE - 8-6-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 2
$150.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
15560
08/18/2025
09/20/2025
2026-00000071
$150.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$150.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Dollar General #4698 -2935-Logan AVE, BLDG 2935 Logan Ave, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
08/0612025
Lead Inspector
BRAD BALDWIN
Inspedtien 7yp
,rF
Other Inspectors
NIA
Shift
N/A
d Street
Inspection Number
14381-R2
Station
NIA
Unit
NIA
SUMMARY OF INSPECTION
i 0
Passed codes
NEXT STEPS
0 1
Resolved violation
0 5
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@watertoo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 07114/2025 @ 12:41
$80.00 annual inspection fee
BRAD BALDWIN - 07114/2025 @ 12:41
-Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
09/05/2025
BRAD BALDWIN - 07/14/2025 @ 12:41
If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for inspections
& re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -inspection fees
start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 07/14/2025 @ 12:41
6/23/25 Site visit with Fire Marshall Weliver to inform store manager to remove alcohol from property per the State due to lack of liquor license.
BRAD BALDWIN - 07114/2025 @ 12:41
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 07/14/2025 @ 12:41
$100 re -inspection fee for corrections incomplete on 7/14/25
BRAD BALDWIN - 08115/2025 @ 15:17
8-6-25. $150 re -inspection fee, failure to complete corrections
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 8/] 5/25, 3:19 PM 1 OF 5
Caress Shears(2025) Date:
CHECKLISTS
BRAD BALDWIN 08/1512025
GENERATED ON 8/15/25, 3'19 PM
2 OF 5
Reinspection
Status
Fail
Fail
Fail
Code
1018.4 - Aisle accessways in Group M.
An aisle accessway shall be provided on not less than one
side of each element within the merchandise pad. The
minimum clear width for an aisle accessway not required to
be accessible shall be 30 inches (762 mm). The required clear
width of the aisle accessway shall be measured perpendicular
to the elements and merchandise within the merchandise
pad. The 30-inch (762 mm) minimum clear width shall be
maintained to provide a path to an adjacent aisle or aisle
accessway. The common path of egress travel shall not
exceed 30 feet (9144 mm) from any point in the merchandise
pad. Exception: For areas serving not more than 50
occupants, the common path of egress travel shall not
exceed 75 feet (22 860 mm).
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Retail aisles
Comments: Maintain 30" clear path in all aisles.
Location: Back storage NW exit door emergency lighting
Comments: Repair or replace emergency lights on exit sign that
failed during testing
Additional comments: Emergency lighting failed test, exit sign did
work today.
Location: Northwest emergency door exit/emergency Tight sign
Comments: Repair or replace sign that failed during testing.
GENERATED ON 8/15/25, 3.19 PM
3 OF 5
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location- NW exterior light near exit
Comments: Repair or replace damaged light fixture hanging by wires.
Location: Near front entrance
Comments: Provide and install extinguisher on wall bracket, no less
than 4" from floor, no more than 5' in height from floor. Extinguisher
signage shall be posted in close proximity to indicate actual location
of extinguisher below.
Additional comments: Provide sign above fire extinguisher hanging
from ceiling grid. Fire extinguisher currently on wall bracket.