COMMERCIAL INSPECTION - 618 SYCAMORE ST - 8-13-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
21840
08/18/2025
09/20/2025
2026-00000066
$80.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Brown Derby - 618 SycamoreST, BLDG 618 Sycamore St, Waterloo IA 50703
INSPECTION DETAILS
inspection Date
08/13/2025
Lead Inspector
BRAD BALDWIN
(MIN Inspectors
N/A
Inspection Type
Annual Inspection (1Yr)
Shift
NIA
[,)U
425 E. 3rd Street
Inspection Number
14786
Station Unit
N/A NIA
SUMMARY OF INSPECTION
Failed codes
NEXT STEPS
0 9`
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/1312025 @ 07:33
$80 annual inspection fee
BRAD BALDWIN - 08/13/2025 @ 07:36
Corrected during 8/12/25 Inspection: (1) Removed beverage fridge from power strip in ballroom, plugged to wall outlet.
BRAD BALDWIN - 08/1312025 @ 07:40
All occupancies in budding- Provide annual service to all fire extinguishers. Ballroom extinguishers due September 2025
BRAD BALDWIN - 08/13/2025 @ 08:22
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (1/5) - Cell: 319-230-1224
BRAD BALDWIN - 08/13/2025 @ 08:25
Reinspection Date
09/03/2025
Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 08/13/2025 `c@ 08:25
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature inspector signature
No signature
Report completed post inspection
kristie Seda 2025 Date: BRAD BALDWIN 08/1312025
t ENERATED ON 3/13/25, 8:27 AM 1 OF 6
CHECKLISTS
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Fire Service Features
Status Code
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Front entry
Comments: Repair or replace emergency egress lights on exit sign
that failed to illuminate during testing.
Location: First floor near office and men's bathroom
Comments: Repair or replace emergency egress lights that failed to
illuminate during testing.
Description
Location: Basement sprinkler system
Comments: Relocate shelf and all obstructions to maintain clear
access for firefighters.
GENERATED ON 8/13/25, 8:27 AM
2 OF 6
Electrical Safety
Status Code
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
Tess, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Liquor room closet
Comments: Remove table obstructing access to electric panel,
maintain 36" clearance in front of panel and clear path to access.
Location: Basement electric service
Comments: Remove obstructions within 36" in front of electric panel,
maintain clear path to access.
GENERATED ON 8/13/25, 8:27 AM
3 OF 6
Fail
Fail
0
Fail
0
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Fire Resistant Construction Maintenance
Status Code
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Fail
0
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.6 - Testing.
Horizontal and vertical sliding and rolling fire doors shall be
inspected and tested annually to confirm proper operation
and full closure. Records of inspections and testing shall be
maintained.
Location: Basement dehumidifier
Comments: Remove power strip from extension cord. Power strip
must be plugged directly to wall outlet.
Location: Liquor room closet
Comments: Remove multi -plug extension cord hanging over electric
panel.
Location: Basement fridge
Comments: Remove extension cord from permanent usage.
Appliance shall be plugged directly to wall outlet. Adding new outlet
would require licensed electrical contractor obtaining permit and
inspection.
Description
Location: 2nd floor kitchenette
Comments: Fire door must completely self -close and latch
Location: 2nd floor women's bathroom
Comments: Fire door must completely self -close and latch
Location: First floor office by men's bathroom
Comments: Remove foot drop down hold open devices from the fire
doors. Must self close and latch. Hold open devices connected to the
fire alarm system are allowed
Location: Elevator fire door
Comments: Provide current annual fire door drop test. Report may be
emailed to fire inspector
GENERATED ON 8/13/25. 8:27 AM 4 OF 6
Portable Fire Extingusihers
Status Code
Fail
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Description
Location: Basement elevator mechanical room
Comments: Provide annual service to fire extinguisher, currently no
tag of service or receipt of date of purchase.
Location: Liquor room closet
Comments: Properly hang fire extinguisher on wall bracket between
4" and 5' from floor.
GENERATED ON 8/13/25, 8:27 AM 5 OF 6