COMMERCIAL INSPECTION - 1024 W 4TH ST - 8-11-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
23189
BILLING DATE
08/18/2025
DUE DATE
09/20/2025
INVOICE #
2026-00000065
CHARGES
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Amani Community Deveolpement - 1024 W 4th ST, BLDG 1024 W 4th St, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
42aas
Lead Inspector
BRAD BALDWIN
Inspection "rype
4nnuaf Inspection (1Yr)
Other Inspectors
N/A
Shift
N/A
Station
N/A
425 E. 3rd Street
inspection Number
17435
Unit
N/A
SUMMARY OF INSPECTION
C 34
Pa' t cnris S,
NEXT STEPS
0 9
Failed c , i
33
NIA c:ocit,s
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/1112025 (ci, 15:13
$100 annual inspection tee
Reinspection Date
09/0512025
BRAD BALDWIN - 08/15/2025 @ 13:56
First floor exit signage options: (1) Remove signs and properly cap electrical in box with cover or provide appropriate covers to signs. (2) Repair or
replace signs that fail to remain illuminated during testing
BRAD BALDWIN - 08/15/2025 @ 14:07
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - COI: 319-230-1224
BRAD BALDWIN - 08/1512025 rt 14:07
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $1.00, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Evelyn Date: BRAD BALDWIN 08/15/2025
CHECKLISTS
GENERATED ON 8/15/25, 2:07 PM 1 OF 6
Means of Egress
status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Additional Codes
Status Code
1010.2.1- Unlatching.
The unlatching of any door or leaf for
egress shall require not require more than one operation
motion in a single linear or rotational direction to release all
latching and all locking devices. Exceptions: 1.Places of
detention or restraint. 2.Where manually operated bolt locks
are permitted by Section 1010.2.5. 3.Doors with automatic
flush bolts as permitted by Section 1010.2.4, Item 3 4. 4.Doors
from individual dwelling units and sleeping units of Group R
occupancies as permitted by Section 1010.2.4, Item 4 5.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures Alt electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
:}esi:riptlon
Location: Front basement stairs
Comments: Remove items on stairs and remove obstructions at base
of stairs to maintain clear path of travel of egress.
tiescriptaati
Location: Front entrance doors
Comments: Reconfigure locks/latches to door to avoid more than one
motion to unlock and unlatch. Currently deadbolt and separate
latching handle requires two motions.
Location: Southwest corner office
Comments: Remove microwave from power strip. Appliance shall be
plugged directly to wall outlet.
GENERATED ON 8/15/25, 2:07 PM 2 OF 6
Emergency Equipment
atus: Code
e
Fail
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Location: Basement at bottom of carpeted stairs
Comments: Repair or replace emergency egress lighting that failed to
illuminate during testing.
Location: Basement carpeted room
Comments: Repair or replace exit sign and emergency egress
lighting that failed to illuminate during testing
Location: Exit signs
Comments: Main floor exit signs not required per occupancy. See
notes for further details.
GENERATED ON 8/15/25, 2:07 PM
3 OF 6
Electrical Safety
Status Code
Fail
O
Fai I
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: North pink carpeted room
Comments: Make necessary repairs or replace outlet that shows
signs of damage on north wall.
Location: Basement bookshelf
Comments: Provide cover to light switch box to avoid shock hazard.
GENERATED ON 8/15/25, 2:07 PM
4 OF 6
Portable Fire Extingusihers
Status Code
Fail
0
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Gescdiptio
Comments: Provide annual service to or replace all fire extinguishers
with new. Purchasing extinguishers personally, not through
contractor requires receipt of purchase taped to bottom of
extinguisher. Most current service completed in 2013.
GENERATED ON 8/15/25, 2:07 PM
5 OF 6
Statement of Fees
FEE
Invoice Date Inspection Fee
NIA $100.00
Date Paid Amount Paid
invoice Number
NIA
Check Number
NIA
Transaction Number
NIA
GENERATED ON 8/15/25, 207 PM