COMMERCIAL INSPECTION - 403 FRANKLIN ST - 8-19-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2.000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23123
09/10/2025
10/15/2025
2026-00000134
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Taqueria Los Reyes - 403 Franklin ST, BLDG 403 Franklin St - STE C, Waterloo IA
50703
INSPECTION DETAILS
Inspection Date
08/19/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
17501
Shih Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 46
Passed codes
NEXT STEPS
0 5
Failed codes
23
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/20/2025 @ 08:52
$80 annual inspection fee
BRAD BALDWIN - 08/2012025 @ 09:22
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 08/20/2025 @ 09:22
Reinspection Date
09/10/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
22.
Antonio Islas Date: BRAD BALDWIN 08/2012025
CHECKLISTS
GENERATED ON 8/20/25, 9:39 AM 1 OF 6
Fire Service Features
Status Code
Fail
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Location: Kitchen near rear door
Comments: Remove obstructions obstruction view of fire
extinguisher and hood suppression pull station, maintain clear path
of access.
GENERATED ON 8/20/25, 9:39 AM
2 OF 6
Electrical Safety
SratuS Cude
Fail
rX
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not Tess than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Location: Kitchen near rear door
Comments: Remove obstructions within 36" in front of electric panel
and maintain clear path of access.
GENERATED ON 8/20/25, 9:39 AM
3 OF 6
Additional Codes
Statue} Code
Fail
606.2 - Where required.
A Type I hood shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used
for commercial purposes that produce grease vapors.
Exceptions: 1.Factory-built commercial exhaust hoods that
are listed and labeled in accordance with UL 710, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 7108, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code. Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code, For the
purpose of determining the floor area required to be
ventilated, each individual appliance shall be considered as
occupying not less than 100 square feet (9.3 m2). 3.Where
cooking appliances are equipped with integral down -draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96, a hood shall not be required at or above them. 4.A
Type 1 hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mg/m3
or less of grease when tested at an exhaust flow rate of 500
cfm (0.236 mils) in accordance with UL 7108.
Commercial Cooking Hood Suppression System
Staiw. Code
Fail
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Kitchen cooking appliances
Comments: Relocate cooking equipment producing grease laden
vapors to be within 6 inches inside of outer edges of hood exhaust
system.
Description
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine. Currently 471 days past due as of 8/20/25.
GENERATED ON 8/20/25, 9:39 AM
4 OF 6
Portable Fire Extingusihers
status Code
Fail
906.2 • General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to all fire extinguishers with date
of service documented. Last recorded service November 2023.