COMMERCIAL INSPECTION - 2046 SOVIA DR - 8-19-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
23043
09/10/2025
10/15/2025
2026-00000121
$80.00
Less Prepayment
Total Due --*
City of Waterloo
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
nspection Report
Freddy's - 2046 Sovia DR, BLDG 2046 Sovia Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
0811912025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
N3
425 E. 3rd Sheet
Inspection Number
1119
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 54
Passed codes
NEXT STEPS
0 9
Failed codes
10
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08119/2025 @ 14:15
$80 annual inspection fee
BRAD BALDWIN - 08/19/2025 @ 14:31
Fire extinguishers due annually serviced by March 2026
BRAD BALDWIN - 08/19/2025 @ 15:41
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
09/11/2025
BRAD BALDWIN - 08/19/2025 @ 15:42
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
--z)E
Yolanza Chambers (2025 GM) Date: BRAD BALDWIN 08/2012025
CHECKLISTS
GENERATED ON 8/20/25, 2,58 PM 1 OF 7
Fire Alarm System
Status rode
Fail
Chapter 14 - Inspection, testing, and maintenance
Fire alarm system tested at least annually by licensed
contractor
General Housekeeping
Status Code
Fail
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Fire Sprinkler System
Status Code
Fail
5.2.1- Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed
contractor
Comments: Inspection and service to fire alarm 42 days past due as
of 8119125, Provide inspection report including corrections to
deficiencies to be uploaded to Compliance Engine,
Comments: Provide listed container for oily rags. See attachment for
example.
Desesi0ti on
Comments: Inspection currently 4 days past due and 2 open
deficiencies as of 8/19/25. Provide report of inspection and
corrections to deficiencies to be uploaded to Compliance Engine
GENERATED ON 8/20/25, 2:58 PM 2 OF 7
Fire Service Features
Statu., Cods
Fail
Fail
506.2 - Key box maintenance.
The operator of the building shall immediately notify the fire
code official and provide the new key where a lock is changed
or rekeyed. The key to such lock shall be secured in the key
box.
509.2 - Equipment access.
Approved access shall be provided and maintained for all fire
protection system equipment to permit immediate safe
operation and maintenance of such equipment. Storage, trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Description
Comments: If key changes have been made, notify Fire Department to
update keys for firefighters access to building.
Location: Kitchen sprinkler system
Comments: Remove obstructions and maintain to clear path of
access to sprinkler system.
GENERATED ON 8/20/25, 2:58 PM
3 OF 7
Electrical Safety
St:xtus Code
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Description
Location: West exterior light fixture
Comments: Repair or replace damaged light fixture exposing wires.
GENERATED ON 8/20/25, 2:58 PM
4 OF 7
Fail
0
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
Location: Kitchen electric panels
Comments: Maintain 36" clearance in front of panel and clear path for
access.
Description
Location: Kitchen hood exhaust
Comments: Exhaust system cleaning 836 days past due as of 8/19/25.
Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
GENERATED ON 8/20/25, 2:58 PM
5 OF 7
Fire Resistant Construction Maintenance
Stratus Code
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
rooflceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Kitchen above "Waste Cooking Oil" containment
Comments: Replace missing ceiling tile.