COMMERCIAL INSPECTION - 2820 FALLS AVE - 8-21-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22167
09/10/2025
10/15/2025
2026-00000135
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Three Amigo's - 2820 Falls AVE, BLDG 2820 Falls Ave, Waterloo IA 50701
INSPECTION DETAILS
ir,,,01r h n 001,
0812112025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift
NIA
425 E. 3rd Sheet
Inspection Number
17351
Station Unit
N/A N/A
SUMMARY OF INSPECTION
0 40
Passed codes
NEXT STEPS
0 13
Failed codes
25
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/21/2025 @ 13:12
$80 annual inspection fee
BRAD BALDWIN - 08/21/2025 @ 13:17
Kitchen hood suppression due for service on 914125
BRAD BALDWIN - 08/21/2025 @ 13:25
Commercial kitchen exhaust hood cleaning due 12/10/25
BRAD BALDWIN - 08/21/2025 @ 13:48
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - CeII: 319-230-1224
Reinspection Date
09/12/2025
BRAD BALDWIN - 08121/2025 @ 13:49
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 08/21/2025 @ 13:49
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Thomas Hernadus Date: BRAD BALDWIN 08/2112025
GENERATED ON 8/21/25, 1:52 PM 1 OF 8
CHECKLISTS
Means of Egress
Status Code
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Additional Codes
Status Code
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
Location: West exit door near basement stairs
Comments: Repair or replace door to open with less than 15lbs of
force. Door did not open today.
Description
Comments: Permit issued for outlet installed by Newton Electric
without inspection. Contractor must obtain inspection.
Location: Basement
Comments: Secure CO2 compressed gas cylinders with chain to
avoid tip over.
GENERATED ON 8/21/25, 1:52 PM 2 OF 8
Emergency Equipment
Status Code
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Dining area, Northeast exit.
Comments: Emergency egress lights on exit sign very dim during
testing, repair or replace.
GENERATED ON 8/21/25, 1:52 PM
3 OF 8
Electrical Safety
Status Code
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multipiug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multipiug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Description
Location: Kitchen above dishwasher
Comments: Damaged junction box cover exposing wires shall be
replaced.
Location: Kitchen exhaust hood above cooktop
Comments: Switch cover plate loose to box exposing wires, install
cover back on box.
Location: Dining (east side) above TV
Comments: Remove multi -plug adapter, may replace with properly
mounted or supported power strip with manual reset. Adding outlet
would require permit and inspection obtained by licensed contractor.
Location: Patron waiting area above Coors Light week sign.
Comments: Remove multi -plug adapter, may replace with properly
mounted or supported power strip with manual reset. Adding outlet
would require permit and inspection obtained by licensed contractor.
GENERATED ON 8/21/25, 1:52 PM 4 OF 8
FF�ail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Kitchen near microwave
Comments: Remove extension cord to microwave. Relocate
microwave to plug directly to wall outlet or add outlet by licensed
electrical contractor with obtaining permit and inspection.
GENERATED ON 8/21/25, 1:52 PM
5 OF 8
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Status Code
Fail
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSUIKECA C10.
Location: Kitchen near 6 burner stove
Comments: Remove white multi -plug extension cord, may replace
with power strip with manual reset plugged to wall outlet.
Description
Location: Kitchen hood exhaust filters
Comments: Clean grease filters. currently dripping grease.
GENERATED ON 8/21/25, 1:52 PM
6 OF 8
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Oto,c pilo
Comments: Provide annual service to all fire extinguishers in
building, currently due by August 2025.
Location: Kitchen above chest freezer
Comments: Annually serviced fire extinguisher shall me mounted to
wall bracket where indicating by wall sign.
GENERATED ON 8/21/25, 1:52 PM
7 OF 8