COMMERCIAL INSPECTION - 1816 -20 WILLISTON ST - 9-03-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
21218
09/10/2025
10/15/2025
2026-00000139
S80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
880.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Freedom Tax Service - 1816-1820 Williston AVE, BLDG 1816 Williston Ave - STE
1820, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
09103/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
17599
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
034
Passed codes
NEXT STEPS
0 7
Failed codes
35
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09104/2025 @ 13:19
$80 annual inspection fee
BRAD BALDWIN - 09/11/2025 @ 07:07
Reinspection Date
10/02/2025
Per occupancy load: Exit signage in suite not required, may be removed by capping wires and containing in box or properly covering sign. If exit signs
remain uncovered, signs shall be maintained to operate properly as manufactured.
BRAD BALDWIN - 09/11/2025 @ 07:20
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09/11/2025 @ 07:20
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jim Lyons Date:
CHECKLISTS
BRAD BALDWIN 09/1112025
GENERATED ON 9/11/25, 7:25 AM 1 OF 5
Means of Egress
Status Code
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Additional Codes
Status Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Back exit
Comments: Remove ladder in front of exit door, maintain clear path
to exit at all times.
Oescriphon
Comments: Provide permit and inspections by licensed building and
electrical contractors for interior walls and electric installed without
permits.
Location: Toaster in back storage area
Comments: Remove toaster from power strip. Appliances with
heating elements shall be plugged directly to wall outlet. Power strips
allowed for light duty only.
Description
Location: All exit signs
Comments: Repair or replace exit signs that failed to illuminate
during test, or.... Further details in notes.
GENERATED ON 9/11/25, 7:25 AM
2 OF 5
Electrical Safety
Status Code
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Descriptic
Location: Desk nearest front entrance
Comments: Remove power strip from white extension cord. Power
strips with manual resets must be plugged directly to wall outlets,
allowed for light duty electric only.
Location: Denise's desk
Comments: Remove power strip from another power strip. Power
strips with manual resets must be plugged directly to wall outlets,
allowed for light duty electric only.
GENERATED ON 9/11/25, 7:25 AM
3 OF 5
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Comments: Provide annual service to fire extinguishers, last current
service recorded 2021.
GENERATED ON 9/11/25, 7:25 AM