COMMERCIAL INSPECTION - 1816-1820 WILLISTON AVE - 9-3-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12189
09/10/2025
10/15/2025
2026-00000140
Less Prepayment
Total Due —>
City of Waterloo
$80.00
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Balkan Cafe - 1816-1820 Williston AVE, BLDG 1816 Williston Ave - STE 1816,
Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
09103/2025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other inspectors
N/A
Shift
NIA
425 E. 3rd Street
Inspection Number
3711
Station Unit
N/A NIA
SUMMARY OF INSPECTION
0 41
Passed codes
NEXT STEPS
0 15
Failed codes
24
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/03/2025 @ 14:57
$80 annual inspection fee
BRAD BALDWIN - 09/03/2025 @ 15:00
Fire extinguishers due annually serviced by April 2026.
BRAD BALDWIN - 09/11/2025 @ 06:56
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09111/2025 @ 06:56
Reinspection Date
10/10/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Q7
Irma Duric (2025) Date: BRAD BALDWIN 09/11/2025
CHECKLISTS
GENERATED ON 9/11/25, 7:24 AM 1 OF 5
General Housekeeping
Swtos Code
304.3.1 - Spontaneous ignition.
Materials susceptible to spontaneous ignition, such as oily
rags, shall be stored in a listed disposal container. Contents
of such containers shall be removed and disposed of daily.
Additional Codes
Status Code
Fail
V
Fail
Fail
3107.12.1 - Installation.
Heating or cooking equipment, tanks, piping, hoses, fittings,
valves, tubing and other related components shall be
installed as specified in the International Fuel Gas Code and
the International Mechanical Code , and shall be approved by
the fire code official.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
ntrtlon
Location: Kitchen
Comments: Provide listed container for oily rag disposal. See
attachment.
De SCriiniun
Location: Auxiliary exhaust fan
Comments: Provide documents for proper installation of fan.
Location: Pizza warmer behind check-out
Comments: Appliance shall be plugged directly to wall outlet,
currently plugged to power strip. Power strips allowed for light duty
electric only. If adding outlet, licensed electrical contractor must
obtain permit and inspection.
Location: Coffee maker behind check-out
Comments: Appliance shall be plugged directly to wall outlet,
currently plugged to power strip. Power strips allowed for light duty
electric only. If adding outlet, licensed electrical contractor must
obtain permit and inspection.
GENERATED ON 9/11/25, 7:24 AM 2 OF 5
Electrical Safety
Status Code
Fail
0
Fail
Fail
0
Fail
Fail
Fail
603.2 - Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Description
Location: Kitchen salad fridge
Comments: Remove fridge from power strip, plug directly to wall
outlet. Power strips allowed for Tight duty electric only.
Location: Soffit lighting above outdoor seating
Comments: Provide bulb for open light socket.
Location: Outlet under small fryer
Comments: Remove yellow 3-plug adapter. May use properly
supported or mounted power strip with manual reset plugged directly
to wall outlet for light duty electric only.
Location: Checkout stand
Comments: Power strip plugged to extension cord shall be corrected.
Properly mounted or supported power strips with manual reset shall
be plugged directly to wall outlet, for light duty electric only. If adding
outlet, licensed electrical contractor must obtain permit and
inspections.
Location: Under pizza warmer
Comments: Mount power strip to cabinet wall or support on shelf to
avoid hanging by wires.
Location: Bathroom hallway closet
Comments: Remove extension cord to chest freezer, relocate freezer
to plug directly to wall outlet or add outlet. Adding outlet requires
licensed electrical contractor to obtain permit and inspections.
GENERATED ON 9/11/25, 7:24 AM 3 OF 5
Fail
Fail
Fail
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Stdtus Code
Fail
606.3.3.2 - Grease accumulation.
If during the inspection it is found that hoods, grease -removal
devices, fans, ducts or other appurtenances have an
accumulation of grease, such components shall be cleaned in
accordance with ANSIIIKECA C10.
Location: Bathroom hallway closet
Comments: Green extension cord allowed for temporary use only.
Currently plugged to kitchen freezer.
Location: Checkout stand
Comments: Remove yellow extension cord plugged to power strip,
extension cords only for temporary use.
Location: Near large kitchen freezer
Comments: Mixer and chest freezer appliances shall be plugged
directly to wall outlets, remove extension cords.
Location: Auxiliary exhaust fan
Comments: Remove extension cord to exhaust system, approved for
temporary use only.
Description
Location: Kitchen hood exhaust filters.
Comments: Close gaps in grease filters by replacing missing filters.
Filters not in place cause more grease in ductwork and on cables for
fire supression.
GENERATED ON 9/11/25, 7:24 AM
4 OF 5
4