COMMERCIAL INSPECTION - 1818 LA PORTE RD - 8-25-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
11210
09/10/2025
10/15/2025
2026-00000129
$80.00
Less Prepayment
Total Due —
City of Waterloo
$0.00
S80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Panera Bread - 1818 La Porte RD, BLDG 1818 La Porte Rd, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
08125/2025
Lead Inspector
BRAD BALDWIN
Other Inspectors
NIA
Inspection Type
Annual Inspection (1Yr)
425 E. 3rd Street
Inspection Number
1117
Shin Station Unit
N/A NIA N/A
SUMMARY OF INSPECTION
45
Passed codes
NEXT STEPS
CD7 Q24
Failed codes N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/26/2025 @ 10:36
$80 annual inspection fee
BRAD BALDWIN - 08/26/2025 @ 10:44
Fire extinguishers due annually serviced February 2026.
BRAD BALDWIN - 08/26/2025 @ 10:50
Reinspection Date
09/19/2025
Corrected during 8125/25 inspection: Removed multiple boxes in path of egress to kitchen back door. Maintain clear path at all times.
BRAD BALDWIN - 08/26/2025 @ 11:05
• If ail corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 08/26/2025 @ 11:05
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jacob Simpson (2025) Date:
CHECKLISTS
BRAD BALDWIN 08/26/2025
GENERATED ON 8/26/25, 11:07 AM 1 OF 5
Emergency Equipment
Status Code
Fail
x
Fail
Fail
x
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
gdesseption
Location: Outside bathrooms
Comments: Provide test documentation with signature and date with
repairs necessary to emergency egress lights. Can not currently
reach test button.
Location: Above dishwashing station
Comments: Repair or replace exit sign that failed to illuminate during
testing.
Location: Entrance to patron bathroom hallway
Comments: Repair or replace exit sign that failed to illuminate during
test.
GENERATED ON 8/26/25, 11:07 AM 2 OF 5
Additional Codes
Status Code
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
603.2.1- Modified or damaged.
Electrical wiring, devices, equipment and appliances that are
modified or damaged, and constitute an electrical shock or
fire hazard, shall not be used until repaired or replaced in
accordance with this code and NFPA 70 .
Location: Dumpster area storage room
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: Bread slicer cord
Comments: Licensed electrical contractor shall repair or replace
damaged cord. Relocate appliance to avoid future damage or provide
UL listed floor cord protector. Retain receipt from contractor of work
completed.
GENERATED ON 8/26/25, 11:07 AM
3 OF 5
Electrical Safety
Status Code Description
Fail 603.4 - Working space and clearancesclearance.
0 A working space of not Working space around electrical Location: Kitchen electric panels
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or Comments: Remove obstructions within 36" in front of panels,
maintain clear path at all times.
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Fire Resistant Construction Maintenance
S?ntu5
Fail
Code Description
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Location: Dumpster area storage room
Comments: Remove foot hold -open device from door.
GENERATED ON 8/26/25, 11:07 AM
4 OF 5
Statement of Fees
FEE
Invoice Date
N/A
Invoice Number
N/A
Inspection Fee
S80.00