COMMERCIAL INSPECTION - 2100-2102 LAFAYETTE - 10-1-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
13067
BILLING DATE
10/17/2025
DUE DATE
11/25/2025
INVOICE #
2026-00000163
CHARGES
$80.00
Less Prepayment
Total Due -�
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Neighborhood Mart - 2100-2102 Lafayette AVE, BLDG 2100-2102 Lafayette Ave,
Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
10/01/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
Shift
NIA
425 E. 3rd Street
Inspection Number
15419
Station Unit
NIA NIA
SUMMARY OF INSPECTION
044 07
Passed codes Failed codes
NEXT STEPS
0 24
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10102/2025 @ 15:27
$80 annual inspection fee
BRAD BALDWIN - 10/02/2025 @ 15:29
Fire extinguishers serviced in September 2025
BRAD BALDWIN - 10103/2025 @ 08:13
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 10/03/2025 @ 08:14
Reinspection Date
10/2412025
• Provide corrections to avoid progressive re -inspection fees beginning at $100. BeerlLiquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 10103/2025 @ 08:14
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Joyce Utsler
CHECKLISTS
No signature
Report completed post inspection
tt�
Date: BRAD BALDWIN 10/03/2025
GENERATED ON 10/3/25, 8:33 AM 1 OF 5
Additional Codes
Sta... CoCie
Fail
1024.1 - Exit passagewaysGeneral.
Exit passageways serving as an exit component in a means
of egress system shall comply with the requirements of this
section. An exit passageway shall not be used for any
purpose other than as a means of egress and a circulation
path.
Description
Location: 2nd exit hallway
Comments: No storage in marked exit hallway allowed, remove
storage. Would be approved, per City Building Official and
occupancy load to remove exit sign, removing exit sign would then
allow storage in hallway.
GENERATED ON 10/3/25, 8:33 AM 2 OF 5
Electrical Safety
S._A.t_ Code
Fail
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Description
Location: East exterior outlet
Comments: Provide proper cover to outlet.
Location: Back office
Comments: Remove obstructions to clear path of access to electric
panel.
Location: Behind register counter
Comments: Remove power strip plugged to other power strip, strips
shall be plugged directly to wall outlet for light duty electric only.
GENERATED ON 10/3/25, 8:33 AM 3 OF 5
Commercial Cooking Hood Suppression System
Status Cod_
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
Portable Fire Extingusihers
Fail
Fail
906.8 - Cabinets.
Cabinets used to house portable fire extinguishers shall not
be locked. Exceptions: 1.Where portable fire extinguishers
subject to malicious use or damage are provided with a
means of ready access. 2.In Group 1-3 occupancies and in
mental health areas in Group 1-2 occupancies, access to
portable fire extinguishers shall be permitted to be locked or
to be located in staff locations provided that the staff has
keys.
906.8 - Cabinets.
Cabinets used to house portable fire extinguishers shall not
be locked. Exceptions: 1.Where portable fire extinguishers
subject to malicious use or damage are provided with a
means of ready access. 2.In Group 1-3 occupancies and in
mental health areas in Group 1-2 occupancies, access to
portable fire extinguishers shall be permitted to be locked or
to be located in staff locations provided that the staff has
keys.
Description
Location: Kitchen hood exhaust cleaning
Comments: Exhaust system cleaning 9 days past due as of 1013/25.
Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Description
Location: Near gas pumps 3&4
Comments: Cabinet glass broken shall be replaced. Glass hammer
missing shall be replaced.
Location: Front of building
Comments: Cabinet glass broken shall be replaced. Glass hammer
missing shall be replaced.
GENERATED ON 10/3/25, 8:33 AM