COMMERCIAL INSPECTION - 2034 LA PORTE - 10-1-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 3
Total Price
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12855
10/17/2025
11/25/2025
2026-00000156
$200.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E. 3rd Street
Hampton Inn & Suites - 2034 La Porte RD, BLDG 2034 La Porte Rd, Waterloo IA
50702
INSPECTION DETAILS
Inspection Date
10101/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr) LREINSPECTION J
Other Inspectors
NIA
Inspection Number
13671-R9
Shift Station Unit
N/A NIA NIA
SUMMARY OF INSPECTION
0o
Passed codes
NEXT STEPS
0 3
Resolved violations
0 11
Failed codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 08/2512025 @ 08:04
$200 re -inspection fee, failure to correct deficiencies as of 8/22/25.
BRAD BALDWIN - 08/2512025 @ 08:04
$200 Re -inspection fee for failure to correct violations on 6/23/25
BRAD BALDWIN - 08/25/2025 @ 08:04
Provide corrections to avoid re -inspection fees
BRAD BALDWIN - 08125/2025 @ 08:04
Annual inspection $235
BRAD BALDWIN - 08/25/2025 @ 08:04
Provide corrections to avoid re -inspection fees.
BRAD BALDWIN - 08/25/2025 @ 08:04
Re -inspection fee $100
BRAD BALDWIN - 08/25/2025 @ 08:04
Corrections not made on fire sprinkler, standpipe, or fire alarm and no date for completion of fire door certifications.
BRAD BALDWIN - 08/25/2025 @ 08:04
Re -inspection fee $150
BRAD BALDWIN - 08/25/2025 @ 08:04
Called Mitch on 4/17125 and he stated no improvement.
BRAD BALDWIN - 08/25/2025 @ 08:04
Re -inspection fee $200
Reinspection Date
10/2412025
GENERATED ON 10/3/25, 9:02 AM 1 OF 9
BRAD BALDWIN - 08125/2025 @ 08:04
annual inspection S200
BRAD BALDWIN - 08/25/2025 @ 08:04
We are recommending denial of alcohol license to the City Council because of lack of progress on required certification of guest room fire doors that
were altered during construction.
BRAD BALDWIN - 08125/2025 @ 08:04
$200 Re -inspection fee, failure to complete corrections as of 7/22125
BRAD BALDWIN - 10103/2025 @ 09:00
$200 re -inspection fee, failure to correct deficiencies or provide plan to make corrections as of 1013/25.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Cayenne Adams - Manager
CHECKLISTS
Date: BRAD BALDWIN 10/0312025
GENERATED ON 10/3/25, 9:02 AM 2 OF 9
Reinspection
Status Code
Fail
Fail
®
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
704.1- Maintaining protection.
Where required when the budding was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Entire buiding
Comments: Obtain permits and inspections for all work concerning
fire door repair, replacement smoke seals, all hardware replaced.
Please see original attached email with codes concerning information
requiered for fire door hardware. Please contact Building Official
Greg Ahlhelm with questions. 319-291-4319
Location: Entire second floor guest fire doors
Comments: Install approved smoke seal in all fire door openings that
has been removed including stair doors and utility areas. Check all
other floors
GENERATED ON 10/3/25. 9:02 AM
3 OF 9
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: 1st floor outside of elevators
Comments: Repair ceiling with sheetrock, mud and tape. Staff did
indicate more ceiling will need removed to complete leak on sprinkler
pipe. Repair will require a permit and inspection.
GENERATED ON 10/3/25, 9:02 AM
4 OF 9
Fail
Fail
704.1- Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire Second Floor
Comments: verify all removed smoke seals have been replaced on
second floor. Also 4th floor and all other smoke sweeps added to
bottom of doors must be verified as listed for fire doors and
inspected.
Location: obtain permit and inspections
GENERATED ON 10/3/25, 9:02 AM 5 OF 9
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction.1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Entire 4th Floor Fire Doors
Comments: Repair or replace fire doors that are improperly installed.
Doors must seal all sides including top and botom to prevent
smoke/fire from inflitrating fire rated coridoor.
GENERATED ON 10/3/25, 9:02 AM
6 OF 9
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Location: Stairway Fire Door by room 330
Comments: Repair fire door. There is a gap at bottom of door. Must
completely seal
Location: Guest Computer Room
Comments: patch sheetrock ceiling with sheetrock. Mud and tape
joints.
Additional comments: No inspection has been completed, contractor
shall request inspection by Chief Building Inspector, Brian Wirtz.
Cayenne stated repair has been completed.
GENERATED ON 10/3/25, 9:02 AM 7 OF 9
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Additional Codes
Status
Fail
Code
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: 1st floor west stair tower door
Comments: Fire rated door altered by cutting bottom of door as
shown in picture. Either replace door by obtaining permit and
inspection or obtain architect to review door, report from architect
shall be sent to inspector.
Location: 1st floor hallway men's bathroom
Comments: Door failed to shut and latch from full open position.
Bottom of door drags and sticks on ground.
Description
Location: 2nd floor laundry room
Comments: Install wall bracket and hang extinguisher within 4" to 5'
from floor. Currently sitting on counter inside laundry room.