COMMERCIAL INSPECTION - 2126 KIMBALL - 10-1-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12084
10/17/2025
11/25/2025
2026-00000158
$80.00
Less Prepayment
Total Due —*
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
, Waterloo Fire Rescue
Inspection Report
Hy-Vee Wine & Spirits #1 - 2126 Kimball AVE, BLDG 2126 Kimball Ave, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
10/01/2025
Lead inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
i-ac
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
14936
Shift Station Unit
N/A NIA N/A
SUMMARY OF INSPECTION
052 06 ®21
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN -10/02/2025 @ 13:36
$80 annual inspection fee
BRAD BALDWIN - 10/02/2025 @ 13:37
Fire extinguishers annually serviced May 2025 by Hawkeye Fire & Safety.
BRAD BALDWIN - 10/02/2025 @ 15:11
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/23/2025
BRAD BALDWIN - 10/02/2025 @ 15:11
• Provide corrections to avoid progressive re -inspection fees beginning at $100. BeerlLiquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 10102/2025 @ 15:11
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Jake Dryer 2025
CHECKLISTS
Date: BRAD BALDWIN 10/02/2025
GENERATED ON 10/2/25, 3:14 PM
1 OF 6
O
Fail
Additional Codes
Status Code
Fail 603,1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Back storage room microwave
Comments: Microwave shall be plugged directly to wall outlet,
remove from power strip.
Location: Red Bull & Monster beverage fridge near cashier
Comments: Appliances shall be plugged directly to wall outlet,
currently plugged to power strip. Power strips approved for light duty
electric only.
GENERATED ON 10/2/25, 3:14 PM
2 OF 6
Faif
Fail
6107.3 - Clearance to combustibles.
Weeds, grass, brush, trash and other combustible materials
shall be kept not less than 10 feet (3048 mm) from LP -gas
tanks or containers.
Location: Front of building LP cabinet
Comments: Relocate firewood to maintain 10 feet of minimum
distance from LP tank cabinet.
6109.12 - Location of storage outside of buildings.
Storage outside of buildings of LP -gas containers awaiting
use, resale or part of a cylinder exchange program shall be
located in accordance with Table 6109.12.
i?i RS l`r
THURSDAY
Location: Outdoor LP storage cabinet
Comments: Provide documentation of maximum quantity (pounds) of
LP allowed in storage cabinet. More than 2500 Ibs of LP storage
requires 10 feet minimum distance from doorway or opening to the
building.
GENERATED ON 10/2/25, 3:14 PM
3 OF 6
Electrical Safety
Status Code
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Back storage room
Comments: Remove objects including fridge in front of electric panel,
maintain path to as well as 36" in front of and 30" in width of
clearance to panels at all times.
GENERATED ON 10/2/25, 3:14 PM
4 OF 6
_Fire.r?osistant Construction Maintenance
Status
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Back storage room door
Comments: Carefully remove paint on fire rating tag on door without
altering tag information.
GENERATED ON 10/2/25, 3:14 PM
5 OF 6
Statement of Fees