COMMERCIAL INSPECTION - 40 W SAN MARNAN - 10-6-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 20,000
OCCUPANCY FEE
Total Price
$90.00
$10.00
CUSTOMER #
6854
BILLING DATE
10/17/2025
DUE DATE
11/25/2025
INVOICE #
2026-00000153
CHARGES
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Fareway Store #951 - 40 W San Marnan DR, BLDG 40 W San Marnan Dr, Waterloo IA
50701
INSPECTION DETAILS
Inspection Date
10/06/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
to :?6
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
15264
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 58 0 6 ® 12
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 10/06/2025 @ 14:30
$100 annual inspection fee
BRAD BALDWIN - 10/06/2025 @ 14:32
Fire extinguishers due annually serviced in June 2026.
BRAD BALDWIN - 10/07/2025 @ 08:10
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/29/2025
BRAD BALDWIN-10107/2025 @ 08:11
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN -10/07/2025 @ 08:11
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
Allen Weimerskich
CHECKLISTS
No signature
Report completed post inspection
Date: BRAD BALDWIN 10/08/2025
GENERATED ON 10/8/25, 3:52 PM 1 OF 5
Means of Egress
Status Code
Fail
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Description
Location: Northwest exit door by milk cooler
Comments: Repair or replace door to open with less than 15lbs of
force. Failed to open easily today.
Description
Location: Exit sign above main exit
Comments: Repair or replace sign that failed to illuminate during
testing.
GENERATED ON 10/8/25, 3:52 PM 2 OF 5
Additional Codes
status Cod.
Fail
5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
Description
Location: South exterior of building
Comments: Provide replacement NFPA 704 signage for current faded
sign.
How to Exchange
Your Propane Tank
LEAYE EMPTY TANK HERE
PAT OASN�ER IN STORE
wt crurogt�-_:-,
0 OETUM TO TNIS DISPLAY
GENERATED ON 10/8/25, 3:52 PM
3 OF 5
Fail 912.2.2 - Existing buildings.
On existing buildings, wherever the fire department
connection is not visible to approaching fire apparatus, the
fire department connection shall be indicated by an approved
sign mounted on the street front or on the side of the
building. Such sign shall have the letters "FDC" not less than
6 inches (152 mm) high and words in letters not less than 2
inches (51 mm) high or an arrow to indicate the location.
Such signs shall be subject to the approval of the fire code
official.
Electrical Safety
Cca_
Fail 603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fail 603.5 - Relocatable power taps and current taps.Multiplug
adapters.
Multiplug adapters, such as cube adapters, unfused plug
strips or any other device not complying with NFPA 70 shall
be prohibited. The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Location: NE corner exterior corner of building
Comments: Options to address "FDC" not visible from road as
discussed with Allen: (1) Remove trees next to building blocking
visibility of "FDC". (2) Permanent sign to be posted on street side
(Brookeridge Dr) per code size requirements including arrow pointing
towards FDC. Sign shall be red with white lettering, will not approve
laminated paper.
Description
Location: Ice chest near liquor shelves
Comments: Remove multi -plug adapter that ice chest is plugged to,
appliance shall be plugged directly to wall outlet. Adding outlet
requires licensed electrician obtaining proper permit and inspections.
Location: Kitchen office printers
Comments: Remove multi -plug adapter that printers are plugged to,
appliance shall be plugged directly to wall outlet. Adding outlet
requires licensed electrician obtaining proper permit and inspections.
GENERATED ON 10/8/25, 3:52 PM
4 OF 5