COMMERCIAL INSPECTION - 1215 ANSBOROUGH - 10-1-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 1
$100.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
6293
10/17/2025
11/20/2025
2026-00000142
$100.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$100.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
3
Waterloo Fire Rescue
nspection Report
Burger King - 1215 Ansborough AVE, BLDG 1215 Anborough Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
10/01/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
REINSPECTION
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
17230-R3
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
0 0 0 4
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/03/2025 @ 11:50
$100 re -inspection fee, failure to correct violations.
BRAD BALDWIN - 09/03/2025 @ 11:50
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
10/31/2025
BRAD BALDWIN - 09/03/2025 @ 11:50
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 09/03/2025 @ 11:50
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 09/03/2025 @ 11:50
$80 annual inspection fee
BRAD BALDWIN - 09/03/2025 @ 11:50
No re -inspection fee today 8/13125, progress made on corrections.
BRAD BALDWIN - 10/01/2025 @ 12:43
$150 re -inspection fee, failure to correct violations. Complete corrections to avoid reoccurring inspection fees.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 10/1/25, 12:47 PM 1 OF 5
Daytoviane McLemore (2025) Date:
CHECKLISTS
Rk'
BRAD BALDWIN 10/01/2025
GENERATED ON 10/1/25, 12:47 PM 2 OF 5
Reinspection
Status Code
Fail
Fail
Fail
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
606.3.3.1 - Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
inspections shall be completed by qualified individuals.
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Kitchen hood exhaust
Comments: Exhaust system cleaning 13 days past due as of 9/3/25.
Provide cleaning and report to be uploaded to Compliance Engine
with any deficiencies corrected.
Additional comments: Currently 41 days past due as of 10/1/25
Location: Kitchen hood suppression system
Comments: Provide suppression system inspection report with any
deficiencies corrected. Contractor must upload report to Compliance
Engine.
Additional comments: Currently 234 days past due as of 1011/25
Location: All fire extinguishers
Comments: Provide annual service to fire extinguishers. Past due as
of Feb 2025
NATIONWIDE
FIRE 8 SAFETY LLC
636-812-2183
ofterdenatjormioe,us -
LICENSE NO St. Louis city CI
kiwi j ! STs1 ltr?
GENERATED ON 10/1/25, 12:47 PM
3 OF 5
Fail 906.4.2 - Class K portable fire extinguishers for deep fat
fryers.
Where hazard areas include deep fat fryers, listed Class K
portable fire extinguishers shall be provided as follows: 1.For
up to four fryers having a maximum cooking medium capacity
of 80 pounds (36.3 kg) each: one Class K portable fire
extinguisher of a minimum 1.5-gallon (6 L) capacity. 2.For
every additional group of four fryers having a maximum
cooking medium capacity of 80 pounds (36.3 kg) each: one
additional Class K portable fire extinguisher of a minimum
1.5-gallon (6 L) capacity shall be provided. 3.For individual
fryers exceeding 6 square feet (0.55 m2) in surface area:
Class K portable fire extinguishers shall be installed in
accordance with the extinguisher manufacturer's
recommendations.
Location: Kitchen class K extinguisher
Comments: Provide annual service to extinguisher.