COMMERCIAL INSPECTION - 3231 W 9TH - 9-11-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 50,000
OCCUPANCY FEE
Total Price
$225.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
3613
10/17/2025
11/20/2025
2026-00000144
$235.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$235.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Columbus High School - 3231 W 9th ST, BLDG 3231 W 9th St, Waterloo IA 50702
INSPECTION DETAILS
n.speotion Date
09/11/2025
ead inspector
BRAD BALDWIN
inspection Type
Biennial Inspection (2yrs)
Other inspector,
BROCK WELIVER, JEREMIAH VANDYKE
SUMMARY OF INSPECTION
425 E. 3rd
Inspection Number
11568
Shift Station Unit
NIA NIA NIA
064 09 02
Passed codas Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/12/2025 @ 13:49
Inspection fee= $225.00
BRAD BALDWIN - 09/1112025 @ 15:45
10/1012024 - (Annual) Kitchen Exhaust HARRIS CLEANING SERVICE. Reviewed Compliant
BRAD BALDWIN - 09/11/2025 @ 15:46
2/14/25 - (Annual) Fire Alarm HAWKEYE ALARM Reviewed Compliant
BRAD BALDWIN - 09/11/2025 @ 15:47
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09111.12025 @ 15:47
Fire extinguishers annually serviced July 2025.
BRAD BALDWIN - 09/11/2025 @ 15:48
Reinspection Date
10/15/2025
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. ****"Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 09/12/2025 @ 08:53
Stage curtain fire treatment (2021). Next treatment due 2026.
GENERATED ON 9/12/25, 1:49 PM 1 OF 6
:p e•a4a6LaSsee':vaia'ae'a'.e seam<.'aieG;P®
i, Fire It d 1 C I K 11 s5. LLC '!
R r/
I/
rj
Y�
i1
14
I/
FX FabricGuard
Cc ttfleate of It e. imorlt
ITV
u ui.A u.1 M111:tia 13
BRAD BALDWIN - 09/12/2025 @ 13:22
IA
Id
I41
/a
/4
'4
P4
/4
v4
r
I4
ZZ>pspa®
Corrected during 9/11/25 inspection: (1) Removed coffee pot from power strip in room #169. (2) Removed portable A1C from extension cord in media
center.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
1
Adam Plautz - Maintenance Date: BRAD BALDWIN 09/1212025
CHECKLISTS
GENERATED ON 9/12/25, 1:49 PM 2 OF 6
Means of Egress
Fail
0
Code
1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Emergency Equipment
Status Code
Fail
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Documentation
Status i cnu
Fail
403.4.1- First emergency evacuation drill.
The first emergency evacuation drill of each school year shall
be conducted within 10 days of the beginning of classes.
Location: Shop garage
Comments: Repair or replace north exit door that failed to push open
with less than 15Ibs of force. Replacement of door will require
building permit and inspection to be obtained.
Oescription
Comments: Provide documentation of testing all emergency egress
lighting in building with repairs made if needed, including date and
signature of person testing. Report may be emailed to inspector.
Comments: Provide documentation of testing all exit signs in
building with repairs made if needed, including date and signature of
person testing. Report may be emailed to inspector.
Description
Comments: Provide record of first fire drill of school year. Fire drill
shall be completed within first 10 days of each school year.
GENERATED ON 9/12/25, 1:49 PM 3 OF 6
Additional Codes
Status Code
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
610.1,2 - Maintenance.
The lint trap, mechanical and heating components, and the
exhaust duct system of a clothes dryer shall be maintained in
accordance with the manufacturer's operating
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Electrical Safety
Status
Fail
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Fire Resistant Construction Maintenance
Status Cade
Fail
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Shop garage
Comments: Secure compressed gas cylinders with chain to avoid tip
over.
Location: 3 clothes dryers
Comments: Provide documentation of clothes dryer vents cleaned
from the appliance to the exterior of the building. Report shall be
signed and dated and may be emailed to inspector.
Description
Location: Room # 222
Comments: Properly support power strip above microwave or mount
to wall surface to avoid hanging by wires
Description
Location: Double hallway doors outside of gymnasium
Comments: Repair door to fully close, currently hitting frame and
fails to shut completely.
GENERATED ON 9/12/25, 1:49 PM
4 OF 6
Portable Fire Extingusihers
stales Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Room #229
Comments: Provide annual service to fire extinguisher, currently past
due.