COMMERCIAL INSPECTION - 214 HIGH ST - 9-16-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 100,000
OCCUPANCY FEE
Total Price
$600.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
3596
10/17/2025
11/20/2025
2026-00000148
CHARGES
$610.00
Less Prepayment
Total Due —�
City of Waterloo
$0.00
$610.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
East High School - 214 High ST, BLDG 214 High St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
09/16/2025
Lead Inspector
BRAD BALDWIN
Inspection Type
Biennial Inspection (2yrs)
/669 ()'
Other Inspectors
BROCK WELIVER, JEREMIAH VANDYKE
425 E. 3rd Soeet
Inspection Number
11693
Shift Station Unit
NIA NIA NIA
SUMMARY OF INSPECTION
G 65
Passed codes
NEXT STEPS
0 20
Failed codes
2
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 09/16/2025 @ 15:37
$610.00 Inspection fee
BRAD BALDWIN - 09/16/2025 @ 15:38
Fire drill completed 9/11125
BRAD BALDWIN - 09/16/2025 @ 15:39
No deficiencies or past dues on Compliance Engine.
BRAD BALDWIN - 09/16/2025 @ 15:41
Fire extinguishers annually serviced July 2025
BRAD BALDWIN - 09/16/2025 @ 15:42
Clothes dryer vents serviced 3/17/25 by Harris Cleaning
Reinspection Date
10/17/2025
BRAD BALDWIN - 09/17/2025 @ 07:37
Corrected during 9I16/25 inspection: (1) Removed door wedge from fire door room #310. (2) Removed extension cord from power strip in room #116. (3)
Removed fridge from extension cord in Custodial Office. (4) 2nd floor double fire doors near band loft held open by weights, removed.
BRAD BALDWIN - 09/17/2025 @ 12:36
Raker Rhodes completed load test of fire escape with no deficiencies on 7/11/25.
BRAD BALDWIN - 09/18/2025 @ 06:52
Stage curtains due for fire treatment by 6/4/2026. (Per Lieutenant J.D. Van Dyke)
BRAD BALDWIN - 09/18/2025 @ 06:54
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
BRAD BALDWIN - 09/18/2025 @ 06:54
GENERATED ON 9/18/25, 7:09 AM 1 OF 8
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature
No signature
Report completed post inspection
Zach Kelly
CHECKLISTS
Means of Egress
Status Code
Fail
Date:
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Code
Fail
Inspector signature
BRAD BALDWIN
1203.4.3 - Records.
Records of the inspection, testing and maintenance of
emergency and standby power systems shall include the date
of service, name of the servicing technician, a summary of
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
Description
09/18/2025
Location: Loading dock hallway
Comments: Remove all storage in hallway, maintain clear path of
access to egress.
Description
Comments: Provide documentation of testing with repairs made if
needed of all exit signage and emergency egress lighting. Document
shall include signature and date of person completing testing, report
may be emailed to inspector.
GENERATED ON 9/18/25, 7:09 AM 2 OF 8
Additional Codes
Status Code
Fail
Fail
Fail
Fail
Fail
Fail
5003.5 - Hazard identification signs.
Unless otherwise exempted by the fire code official, visible
hazard identification signs as specified in NFPA 704 for the
specific material contained shall be placed on stationary
containers and above -ground tanks and at entrances to
locations where hazardous materials are stored, dispensed,
used or handled in quantities requiring a permit and at
specific entrances and locations designated by the fire code
official.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
705.2.6 - Testing.
Horizontal and vertical sliding and rolling fire doors shall be
inspected and tested annually to confirm proper operation
and full closure. Records of inspections and testing shall be
maintained.
Description
Location: Loading dock
Comments: Provide appropriate signage for large container of
unknown liquid or remove from building.
Location: Nurses room #109
Comments: Fridge, microwave, icemaker, and air fryer shall be
removed from power strip. Appliances shall be plugged directly to
wall outlets. Power strips approved for light duty electric only.
Location: Health room #22
Comments: Remove fridge and microwave from power strip.
Appliances shall be plugged directly to wall outlets. Power strips
approved for light duty electric only.
Location: P.E. office
Comments: Remove fridge and microwave from power strip.
Appliances shall be plugged directly to wall outlets. Power strips
approved for light duty electric only.
Location: ROTC clothing area
Comments: Fridge shall be removed from power strip. Appliances
shall be plugged directly to wall outlets. Power strips approved for
light duty electric only.
Location: Head custodial office
Comments: Microwave shall be removed from power strip. Appliance
shall be plugged directly to wall outlets. Power strips approved for
light duty electric only.
Comments: Provide documentation of testing rolling fire doors,
report may be emailed to inspector.
GENERATED ON 9/18/25, 7:09 AM 3 OF 8
Electrical Safety
Slaws Code
Fail
Fail
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Room #214
Comments: Open wire connection above TV shall be properly
contained in box with cover.
Location: Boiler room
Comments: Install cover on open fitting
GENERATED ON 9/18/25, 7:09 AM
4 OF 8
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.8 - Temporary wiring.
Temporary The use of temporary wiring for electrical power
and lighting installations shall not exceed is allowed for a
period not to exceed of 90 days. Temporary wiring methods
shall meet the applicable provisions of NFPA 70. Exception:
Temporary wiring for electrical power and lighting
installations is allowed complying with the applicable
provisions of NFPA 70 is permitted during periods of
construction, remodeling, repair or demolition of buildings,
structures, equipment or similar activities.
Location: Room #303
Comments: Remove power strip from extension cord. Power strips
shall be plugged directly to wall outlet, allowed for light duty electric
only.
Location: Room #214
Comments: Christmas lights allowed for 90 days, not permanent use.
GENERATED ON 9/18/25, 7:09 AM 5 OF 8
Fire Resistant Construction Maintenance
Status Code
Fail
Fail
Fail
Fail
Fail
l:J
Fail
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2 - Inspection and maintenance.
Opening protectives in fire -resistance -rated assemblies shall
be inspected and maintained in accordance with NFPA 80.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
705.2.4 - Door operation.
Swinging fire doors shall close from the full -open position
and latch automatically.
Description
Location: Joelie Smith band office
Comments: Replace missing ceiling tiles. Repair hole in ceiling above
drop ceiling grid.
Location: 2nd floor to 3rd floor East stairwell
Comments: Replace missing ceiling tile.
Location: Room #107
Comments: Replace missing ceiling tile.
Location: Double fire doors near room #304
Comments: Doors at top of stairs failed to shut and latch today.
Repair or replace doors. Replacement of doors will require permit
and inspection obtained.
Location: Double doors near room #107
Comments: Doors failed to shut and latch today. Repair or replace
doors. Replacement of doors will require permit and inspection
obtained.
Location: 1st floor elevator fire door
Comments: Door failed to self -shut and latch today. Repair or
replace, replacement of door requires permit and inspection
obtained.
GENERATED ON 9/18/25, 7:09 AM 6 OF 8
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group I-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: 4th floor access room above auditorium
Comments: Provide annual service to fire extinguisher, currently past
due.