COMMERCIAL INSPECTION - 210 E TOWER PARK DR - 7-17-25
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
REINSPECTION 3
$200.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10758
07/29/2025
08/05/2025
2026-00000046
$200.00
Less Prepayment
Total Due -->
City of Waterloo
$0.00
$200.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Sam's Club - 210 E Tower Park DR, BLDG 210 E Tower Park Dr, Waterloo IA 50701
INSPECTION DETAILS
/75g
425 E. 3rd Street
Inspection Date Inspection Type Inspection Number
07/17/2025 Annual Inspection (1Yr) (REINSPECTION ) 12174-R5
Lead inspector
BRAD BALDWIN
Other Inspectors
N/A
Shift Station Unit
N/A N/A N/A
SUMMARY OF INSPECTION
0 0 0 1 e 2
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 06/26/2025 @ 07:23
Provide correctins to avoid re -inspection fees
BRAD BALDWIN - 06/26/2025 @ 07:23
annual inspection $600
BRAD BALDWIN - 06/26/2025 @ 07:23
Fire door drop test 5/13/24
BRAD BALDWIN - 06/26/2025 @ 07:23
Fire pump maintenance Elite 2/20/24
BRAD BALDWIN - 06/26/2025 @ 07:23
Fire Alarm inspection due 3/19/25
BRAD BALDWIN - 06/26/2025 @ 07:23
hood fire suppression due 3/30/25
BRAD BALDWIN - 06/26/2025 @ 07:23
Provide corrections to avoid $100 re -inspection fee.
BRAD BALDWIN - 06/26/2025 @ 07:23
No fee today because some work completed. Fees will apply if all corrections not completed.
BRAD BALDWIN - 06/26/2025 @ 07:23
Failure to correct violations may result in re -inspections fees
BRAD BALDWIN - 06/26/2025 @ 07:23
RE-inspeciton fee $100
Reinspection Date
08/07/2025
GENERATED ON 7/17/25, 7:54 AM
1 OF 3
BRAD BALDWIN - 07117/2025 @ 07:50
$150 re -inspection fee, failure to correct violations as of 7117125.
SIGNATURES
Contact signature
No signature
Report completed post inspection
Josh Marx - Club Manager
CHECKLISTS
Reinspection
Coda
Inspector signature
Date: BRAD BALDWIN
Fail 1010.1.3 - Door opening force Forces to unlatch and open
doors.
The force for pushing or pulling open interior swinging
egress doors, other than fire doors, shall not exceed 5
pounds (22 N). These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position. For other swinging doors,
as well as sliding and folding doors, the door latch shall
release when subjected to a 15-pound (67 N) force. The door
shall be set in motion when subjected to a 30-pound (133 N)
force. The door shall swing to a full -open position when
subjected to a 15-pound (67 N) force. The forces to unlatch
doors shall comply with the following: 1.Where door
hardware operates by push or pull, the operational force to
unlatch the door shall not exceed 15 pounds (66.7 N). 2.Where
door hardware operates by rotation, the operational force to
unlatch the door shall not exceed 28 inch -pounds (315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated, other than doors required to be fire rated, the force
for pushing or pulling open the door shall not exceed 5
pounds (22 N). 2.For other swinging doors, sliding doors or
folding doors, and doors required to be fire rated, the door
shall require not more than a 30-pound (133 N) force to be set
in motion and shall move to a full -open position when
subjected to not more than a 15-pound (67 N) force.
Fail 507.5.3 - Private fire service mains and water tanks.
Private fire service mains and water tanks shall be
periodically inspected, tested and maintained in accordance
with NFPA 25 at the following intervals: 1.Private fire hydrants
of all types: Inspection annually and after each operation;
flow test and maintenance annually. 2.Fire service main
piping: Inspection of exposed, annually; flow test every 5
years. 3.Fire service main piping strainers: Inspection and
maintenance after each use. Records of inspections, testing
and maintenance shall be maintained.
Description
0711712025
Location: Exit door by eco lab # 7 and case of shell oil
Comments: Repair exit door. Exit door must unlatch and swing to full
open with less than 15# force. Door would not open at all today. If
replaced obtain permits and inspectcions.
Additional comments: No permit obtained as of 7117125.
Location: Private fire hydrant
Comments: Service for hydrant now 28 days past due as of 6126/25.
Private hydrants need to be inspected by licensed contractor and
report uploaded to Compliance engine by contractor
Additional comments: Provide corrections to open deficiencies noted
on Compliance Engine. Report of corrections shall be uploaded to
Compliance Engine.