COMMERCIAL FIRE INSPECTION - 1221 FRANKLIN ST -
02/ 10/2026
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
21820
02/16/2026
03/23/2026
2026-00000329
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
1182.0
Waterloo Fire Rescue
Inspection Report
Michoacana - 1221 Franklin ST, BLDG 1221 Franklin St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
02/10/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other lnspectors
NIA
425 E. 3rd Street
Inspection Number
16724
Shift Station Unit
NIA N/A NIA
SUMMARY OF INSPECTION
0 39
Passed codes
NEXT STEPS
0 18
Failed codes
24
NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baidwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02116/2026 @ 07:33
• $80 annual inspection fee
BRAD BALDWIN - 02/16/2026 @ 07:33
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/11/2026
BRAD BALDWIN - 02/16/2026 @ 07:33
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 02/16/2026 @ 07:33
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.ln. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature
No signature
Report completed post inspection
Inspector signature
Blanca Garcia Date: BRAD BALDWIN 02/16/2026
CHECKLISTS
GENERATED ON 2/16/26. 7:36 AM
1 OF 11
Means of Egress
Status Cote
Fail
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Description
Location: Back exit hallway
Comments: Remove all storage in hallway.
GENERATED ON 2/16/26, 7:36 AM 2 OF 11
Additional Codes
Fail
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
603.9.1 - Listed and labeled.
Only listed and labeled portable, electric space heaters shall
be used.
Des'rription
Location: Drywall/Firewall Repair Permit (2024)
Comments: Contractor "Pacos Roofing" shall obtain inspection of
work completed.
Location: Keurig coffee machine near register
Comments: Remove coffee machine from extension cord. Appliance
shall plug directly to wall outlet.
Location: Kitchen Keurig coffee machine
Comments: Remove coffee machine from power strip, appliance shall
plug directly to wall outlet.
Location: Mechanical room
Comments: Provide documentation of proper listing and labeling of
commercially approved heater or remove from building. Found
running next to water heater unattended.
GENERATED ON 2/16/26, 7:36 AM
3 OF 11
Fail
606.2 - Where required.
A Type I hood shall be installed at or above all commercial
cooking appliances and domestic cooking appliances used
for commercial purposes that produce grease vapors.
Exceptions: 1.Factory-built commercial exhaust hoods that
are listed and labeled in accordance with UL 710, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 710B, and
installed in accordance with Section 304.1 of the International
Mechanical Code, shall not be required to comply with
Sections 507.1.5, 507.2.3, 507.2.5, 507.2.8, 507.3.1, 507.3.3,
507.4 and 507.5 of the International Mechanical Code. Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403,3.1.1 of the International Mechanical Code. For the
purpose of determining the floor area required to be
ventilated, each individual appliance shall be considered as
occupying not less than 100 square feet (9.3 m2). 3.Where
cooking appliances are equipped with integral down -draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96, a hood shall not be required at or above them. 4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mglm3
or less of grease when tested at an exhaust flow rate of 500
cfm (0,236 m3/s) in accordance with UL 710B.
Emergency Equipment
S at is Code
Fail
1203.2.15 - Means of egress illumination.
Emergency power shall be provided for means of egress
illumination in accordance with Sections 1008.3 and 1104.5.1.
Location: Kitchen
Comments: 6 Burner range must be under Type 1 hood with at least a
6" overlap and protected by fire suppression system. Move range
under hood.
Descr
p
on
Location: Dining room egress light by TV
Comments: Repair or replace egress lighting that failed to illuminate
during test.
GENERATED ON 2/16/26, 7:36 AM
4 OF 11
Electrical Safety
Status Code
Fail
Fail
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not Tess than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1,
Where other dimensions are required or allowed by NFPA 70.
2, Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Description
Location: Kitchen electric closet
Comments: Remove obstructions to door to gain access to electric
room.
Location: Mechanical room
Comments: Power strip above water heater plugged to fan shall be
properly mounted to wall to avoid hanging by wires.
GENERATED ON 2/16/26, 7:36 AM
5 OF 11
Fail
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Mechanical room
Comments: Remove white flexible cord from above concealed space
(above ceiling).
GENERATED ON 2/16/26, 7:36 AM
6 OF 11
Fail
0
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
Status Code
Fail
0
Fail
0
606.3.3 - Cleaning.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be cleaned at intervals as required by
Sections 606.3.3.1 through 606.3.3.3.
606.3.3.1- Inspection.
Hoods, grease -removal devices, fans, ducts and other
appurtenances shall be inspected at intervals specified in
Table 606.3.3.1 or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Location: Kitchen freezer
Comments: Remove white flexible cord from above ceiling. If adding
outlet to replace cord, licensed electrical contractor shall obtain
permit and inspection.
Description
Location: Kitchen hood exhaust
Comments: Provide contractor report including deficiencies
corrected to Compliance Engine, currently 64 days past due. Last
cleaning completed Dec 2025 per hood sticker.
Location: Hood suppression system
Comments: Provide contractor report including deficiencies
corrected to Compliance Engine, currently 10 days past due. Last
inspection completed July 2025 per tag.
GENERATED ON 2/16/26, 7:36 AM 7 OF 11
Fire Resistant Construction Maintenance
status Code
Fail
Fail
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
704.1 - Maintaining protection.
Where required when the building was originally constructed,
materials and systems used to protect joints and voids in the
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire -resistance -rated
walls, floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire harrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Description
Location: Fire door separating from Meat Market
Comments: Repair or replace door that failed to shut and latch.
Replacing door requires obtaining permit and inspection.
Location: Fire door separating from Meat Market.
Comments: Carefully remove paint covering fire door tag without
altering tag information.
GENERATED ON 2/16/26, 7:36 AM
8 OF 11
Portable Fire Extingusihers
Status
Fail
Fail
LJ
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: All extinguishers
Comments: Provide annual service to all extinguishers. Last service
completed in 2024.
Location: Bathroom hallway
Comments: Extinguisher shall be properly mounted on wall bracket
between 4in - 5ft from floor.
GENERATED ON 2/16/26, 7:36 AM
9 OF 11
Fail
906.7 - Hangers and brackets.
Hand-held portable fire extinguishers, not housed in cabinets,
shall be installed on the hangers or brackets supplied.
Hangers or brackets shall be securely anchored to the
mounting surface in accordance with the manufacturer's
installation instructions.
Location: Near register counter
Comments: Extinguisher shall be properly mounted on wall bracket
between 4in - 5ft from floor.