COMMERCIAL FIRE INSPECTION - 1215 FRANKLIN ST -
02/10/2026
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
14785
02/16/2026
03/23/2026
2026-00000328
$80.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Michoacana Meat Market - 1215 Franklin ST, BLDG 1215 Franklin St, Waterloo IA
50703
INSPECTION DETAILS
Inspection Date
02/10/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16383
Shift Station Unit
NIA N/A N/A
SUMMARY OF INSPECTION
0 34 0 6 ®33
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/16/2026 @ 07:17
• $80 annual inspection fee
BRAD BALDWIN - 02/16/2026 @ 07:29
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (45) - CeII: 319-230-1224
Reinspection Date
03/1112026
BRAD BALDWIN - 02/1612026 @ 07:29
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 02116/2026 @ 07:29
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Blanca Garcia Date:
CHECKLISTS
BRAD BALDWIN 02/16/2026
GENERATED ON 2/16/26, 7:33 AM 1 OF 6
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not less than 90 minutes.
General Housekeeping
Status Code
Fail
®
305.1- Clearance from ignition sources.
Clearance between ignition sources, such as luminaires,
heaters, flame -producing devices and combustible materials,
shall be maintained in an approved manner.
Description
Location: Back exit
Comments: Repair or replace exit sign/egress light that failed to
illuminate during test.
Description
Location: Mechanical room
Comments: Remove storage on furnace, maintain 36" clearances at
all times.
GENERATED ON 2/16/26, 7:33 AM 2 OF 6
Electrical Safety
Status Code
Fail
Q
603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Description
Location: Freezer behind meat counter
Comments: Provide plug to opening in box
GENERATED ON 2/16/26, 7:33 AM
3 OF 6
Fail
O
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical Location: Electric panel
equipment shall be provided in accordance with Section Comments: Remove storage below panel and maintain clear path of
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or access at all times.
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
GENERATED ON 2/16/26, 7:33 AM
4 OF 6
Fail
O
603.5.3 - Installation.
Relocatable power tap cords shall not extend through walls,
ceilings, floors, under doors or floor coverings, or be subject
to environmental or physical damage.
Portable Fire Extingusihers
Status Code
Fail
O
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Location: Mechanical room
Comments: Properly mount and support power strip to avoid hanging
by wires.
Description
Location: Fire extinguishers
Comments: Provide annual service to fire extinguishers, last
recorded service in 2023
GENERATED ON 2/16/26, 7:33 AM 5 OF 6