COMMERCIAL FIRE INSPECTION - 37 FLETCHER AVE -
02/ 16/2026
Description
FOR BILLING INQUIRY: (319)291-4323
INSPECTION 2,000
OCCUPANCY FEE
CUSTOMER#
24913
Total Price
$70.00
$10.00
BILLING DATE
02/18/2026
DUE DATE
03/25/2026
INVOICE #
2026-00000337
CHARGES
Less Prepayment
Total Due —>
City of Waterloo
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Ii30
Waterloo Fire Rescue
Inspection Report
Fat Cup - 37 Fletcher AVE, BLDG 37 Fletcher Ave, Waterloo IA 50701
INSPECTION DETAILS
Inspection Date
02/16/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
N/A
425 E. 3rd Street
Inspection Number
20649
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 37
Passed codes
NEXT STEPS
0 6
Failed codes
Q 34
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02116/2026 @ 15:47
• $80 annual inspection fee
BRAD BALDWIN - 02/16/2026 @ 15:47
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/18/2026
BRAD BALDWIN - 02/16/2026 @ 15:47
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Ryan Pierce
CHECKLISTS
Date: BRAD BALDWIN 02/16/2026
GENERATED ON 2/16/26, 3:55 PM
1 OF 4
Emergency Equipment
Status Cede
Fail 1203.2.6 - Exit signs.
OEmergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Fail 1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required load for a duration of not less than 90 minutes.
Additional Codes
Status Code
Fail
Fail
5303.5.3 - Securing compressed gas containers, cylinders
and tanks.
Compressed gas containers, cylinders and tanks shall be
secured to prevent falling caused by contact, vibration or
seismic activity. Securing of compressed gas containers,
cylinders and tanks shall be by one of the following methods:
1.Securing containers, cylinders and tanks to a fixed object
with one or more restraints. 2.Securing containers, cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers, cylinders or tanks.
3. Nesting of compressed gas containers, cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public. Nesting shall be allowed
provided that the nested containers, cylinders or tanks, if
dislodged, do not obstruct the required means of egress.
4.Securing of compressed gas containers, cylinders and
tanks to or within a rack, framework, cabinet or similar
assembly designed for such use. Exception: Compressed gas
containers, cylinders and tanks in the process of
examination, filling, transport or servicing.
603.1.1- Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Fail 603.1.1 - Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment,
wiring, devices and appliances shall be tested; and listed by
an approved agency and labeled; and installed, used and
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Description
Location: Garage
Comments: Repair or replace exit sign and egress light combo that
failed to illuminate during test.
Location: Roasterie
Comments: Repair or replace exit sign and egress light combo that
failed to illuminate during test.
Description
Location: Behind counter and garage
Comments: Secure compressed gas cylinders with chain or strap to
avoid tip over.
Location: Coffee grinder in Roasterie
Comments: Remove grinder from extension cord, appliance shall
plug directly to wall outlet. Owner stated to be relocating grinders by
adding new outlets. Adding outlets requires obtaining proper permit
and inspection.
Location: Beverage fridge at register counter
Comments: Remove fridge from extension cord, appliance shall pug
directly to wall outlet.
GENERATED ON 2/16/26, 3:55 PM
2 OF 4
Portable Fire Extingusihers
Status Code
Fail
906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2,4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.1n Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: All extinguishers
Comments: Provide annual service to extinguishers, all past due for
service.