COMMERCIAL FIRE INSPECTION - 110 E 11TH ST - 02/16/2026
FOR BILLING INQUIRY (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
BILLING DATE
DUE DATE
INVOICE #
CHARGES
22278
02/18/2026
03/25/2026
2026-00000336
$80.00
Less Prepayment
Total Due —+
City of Waterloo
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
titc)
22218
Waterloo Fire Rescue
Inspection Report
Edo's - 110 E 11th ST, BLDG 110 E 11th St, Waterloo IA 50703
INSPECTION DETAILS
Inspection Date
02/16/2026
Lead Inspector
BRAD BALDWIN
Inspection Type
Annual Inspection (1Yr)
Other Inspectors
NIA
425 E. 3rd Street
Inspection Number
16650
Shift Station Unit
NIA NIA N/A
SUMMARY OF INSPECTION
0 41
Passed codes
NEXT STEPS
9
Failed codes
0 25
N/A codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
BRAD BALDWIN - 02/17/2026 @ 13:07
• $80 annual inspection fee
BRAD BALDWIN - 02/17/2026 @ 13:21
Christmas lighting approved for temporary use (90 days)
BRAD BALDWIN - 02/17/2026 @ 13:29
Extinguishers due annually serviced January 2027
BRAD BALDWIN - 02/17/2026 @ 13:30
Inspector not given access to 2 offices near mechanical room
BRAD BALDWIN - 02/17/2026 @ 13:47
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#5) - Cell: 319-230-1224
Reinspection Date
03/12/2026
BRAD BALDWIN - 02/17/2026 @ 13:47
• Provide corrections to avoid progressive re -inspection fees beginning at $100. Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN - 02/17/2026 @ 13:50
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. ""***Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 2/17/26, 1:52 PM
1 OF 7
Edin Sahinovic
CHECKLISTS
Means of Egress
Status Code
Fail
Date:
1032.2 - Reliability.
Required exit accesses, exits and exit discharges shall be
continuously maintained free from obstructions or
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied. An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
BRAD BALDWIN 02/17/2026
Description
Location: llth St exit
Comments: Remove plywood from egress path immediately. Maintain
dear path of egress at all times.
GENERATED ON 2/17/26, 1:52 PM
2 OF 7
Additional Codes
Status Code
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
6103.2.1 - Portable containers.
Portable LP -gas containers, as defined in NFPA 58, shall not
be used in buildings except as specified in NFPA 58 and
Sections 6103.2.1.1 through 6103.2.1.7.
Emergency Equipment
Status Code
Fail
1203.2.6 - Exit signs.
Emergency power shall be provided for exit signs as required
in Section 1013.6.3. The system shall be capable of powering
the required Toad for a duration of not Tess than 90 minutes.
peon
Location: HVAC & electric permits for furnace
Comments: Contractor (Low Dollar) shall obtain inspection of work
completed. Permit obtained 11/13/25, no inspection on record.
Location: Smoking room
Comments: Remove LP heater from building.
Description
Location: storage room by kitchen
Comments: Repair or replace exit sign/egress lights combo that
failed to illuminate during test.
GENERATED ON 2/17/26, 1:52 PM
3 OF 7
Electrical Safety
Status Cede
Fail 603.2.2 - Unapproved conditionsOpen electrical terminations.
Open junction boxes and open -wiring splices shall be
prohibited. Approved covers shall be provided for all switch
and electrical outlet boxes.
Fail 603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
Description
Location: Water heater room
Comments: Install missing outlet cover.
Location: Mechanical room by bathrooms
Comments: Remove obstructions to clear access to electric panel.
36" clear space in front of panel shall be maintained.
GENERATED ON 2/17/26, 1:52 PM
4 OF 7
Fail
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use in a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: DJ Booth
Comments: Remove power strip plugged to another power strip.
Each individual strip shall plug directly to wall outlet.
Location: Kitchen next to fridge
Comments: Remove brown extension cord from permanent usage,
appliances shall plug directly to wall outlet.
GENERATED ON 2/17/26, 1:52 PM
5 OF 7
Portable Fire Extingusihers
Status Cud?
Fail 906.2 - General requirements.
Portable fire extinguishers shall be selected, installed and
maintained in accordance with this section and NFPA 10.
Exceptions: 1.The distance of travel to reach an extinguisher
shall not apply to the spectator seating portions of Group A-5
occupancies. 2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry -chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device, provided that all of the
following conditions are met: 2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned, properly
charged and unobstructed. 2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal. 2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed. 2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10. 3.In Group 1-3, portable fire
extinguishers shall be permitted to be located at staff
locations.
Description
Location: Storage room near kitchen
Comments: Provide annual service to extinguishers, last tagged for
service Feb 2025.
GENERATED ON 2/17/26, 1:52 PM
6 OF 7
Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $80.00
Invoice Number
N/A
Check Number Transaction Number
N/A N/A